INSP-Final Inspection | 2/23/2010 | 2/23/2010 | 2/23/2010 | P | PASS |
Forrest France
|
|
|
UG fire supply line permit work okay for final status per activity notes and overhead system testing for project related FIR's.
|
INSP-Alarm Testing | 12/10/2009 | 12/11/2009 | 12/11/2009 | P | CANC |
Troy Cobbley
|
|
|
Wrong inspection type called in.
|
INSP-Supply line flush | 12/2/2009 | 12/3/2009 | 12/3/2009 | A | PASS |
Troy Cobbley
|
|
|
The underground flush passed.
|
INSP-Sprinkler Rough-in/Hydro | 12/1/2009 | 12/1/2009 | 12/1/2009 | P | PASS |
Troy Cobbley
|
|
|
Underground hydro test passed.
|
INSP-Sprinkler Rough-in | 7/20/2009 | 7/21/2009 | 7/21/2009 | P | PASS |
Troy Cobbley
|
|
|
The 6" underground supply piping is ok to cover.
|
INSP-Sprinkler Rough-in | 7/16/2009 | 7/17/2009 | 7/17/2009 | A | FAIL |
Troy Cobbley
|
|
|
The new 6" underground supply piping does not meet the state requirement of a minumum 4'-6" bury depth. I went over the depth of bury with EKC while on site and contacted Trent with Phoenix Fire. Pipe can not be buried until re-inspected.
|
INSP-Sprinkler Rough-in | 7/16/2009 | 7/16/2009 | 7/16/2009 | P | CANC |
Troy Cobbley
|
|
|
Rescheduled for tomorrow morning due to time constraints today.
|