INSP-Final Inspection | 2/18/2010 | 2/19/2010 | 2/19/2010 | A | PASS |
Troy Cobbley
|
|
|
Permit finaled
|
INSP-Final Inspection | 2/18/2010 | 2/18/2010 | 2/18/2010 | P | FAIL |
Troy Cobbley
|
|
|
Due to time constraits I was unable to complete the entire inspection. The forward flush passed as well as the fire alarm interconnections. Verification of ceiling installation, canopy installation and any possible blocked heads due to light fixtures still needs to be completed.
|
INSP-Sprinkler Rough-in/Hydro | 12/3/2009 | 12/3/2009 | 12/3/2009 | P | PASS |
Troy Cobbley
|
|
|
The sprinkler piping can now be covered.
|
INSP-Sprinkler Rough-in/Hydro | 12/2/2009 | 12/3/2009 | 12/3/2009 | A | PASS |
Troy Cobbley
|
|
|
The overhead piping passed the hydro tests.
|
INSP-Sprinkler Rough-in | 12/1/2009 | 12/2/2009 | 12/2/2009 | P | PART |
Troy Cobbley
|
|
|
Piping is ok to cover except at the top of the vertical risers which will require additional insulation and the voids under both fire places needs filled with insulation as well.
|
INSP-Sprinkler Rough-in | 11/24/2009 | 11/27/2009 | 11/27/2009 | A | PASS |
Troy Cobbley
|
|
|
The previous items on the correction notice have been corrected. The piping still can not be covered until the combustible concealed spaces throughout the facility, including at the fire places have been addressed and the veritical cpvc piping is insulated. These items need to be inspected prior to cover.
|
INSP-Sprinkler Rough-in | 11/23/2009 | 11/24/2009 | 11/24/2009 | A | PART |
Troy Cobbley
|
|
|
All of the attic system was inspected as well as just the east wing of the wet system. In several locations the sidewall heads are too close to one another and once the ceiling is installed may be too close to the ceiling. The contractor needs to contact Tim Frost about changes that could adversely effect the attic system hydraulic calculations. The location of acouple of the upright sprinkler heads need to be modified to provide correct sprinkler coverage. Earthquake bracing needs to be modified so that the "earthquake ears" are not used as discussed.
|