Permit Information
Permit NumberFIR09-00479
StatusFinaled
Name CURTIS FIRE SPRINKLER SERVICE INC
Site Address 2708 E WINDSONG DR
Project NameSchultz Residence
Customer Number 
ePlanReview 
Description
The Fire Sprinkler Scope of work consists of a modified 13D sprinkler system to protect a new residence. The water supply is from a city main. The system utilizes conceal type sprinklers.

Permit for the construction of a one story with basement 3,708 sq. ft. single family dwelling (grade level story 2,535 sq. ft., Basement 1173 sq. ft.) with 4 bedrooms, 3 bathrooms, approximately 400 sq. ft. of covered deck/patio and a 1062 sq. ft. attached garage. All work to be done per the approved plans, plan review report, any notations and the attached engineering. A letter from the applicant's geotechnical engineer indicating that the footing sub-grade is acceptable must be approved by Public Works prior to scheduling a footing inspection. Call Terry Records at 384-3946. R-1A/DA zoning and setbacks per planning. CDM
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection12/11/200912/14/200912/14/2009APASS
DetailsForrest France
Fire sprinkler permit work passed final inspection, contractor to provide "911" sign at the outside bell as discussed.
INSP-Sprinkler Rough-in/Hydro11/24/200911/24/200911/27/2009PPART
DetailsForrest France
Okay to cover overhead per activity notes.
INSP-Sprinkler Rough-in10/28/200910/29/200910/29/2009APASS
DetailsTroy Cobbley
The sprinkler piping is ok for cover. Tenting is complete. Several locations needed to be modified while I waited.
INSP-Sprinkler Rough-in/Hydro10/28/200910/28/200910/28/2009PNR
DetailsForrest France
Insulation work incomplete, not ready for inspection at this time per contractor.
INSP-Sprinkler Rough-in/Hydro10/23/200910/23/200910/23/2009APART
DetailsForrest France
See notes on stamped plan set.
INSP-Sprinkler Rough-in10/21/200910/21/200910/22/2009PPART
DetailsForrest France
Duplicate, see site inspection comments 10/22.
INSP-Sprinkler Rough-in/Hydro10/22/200910/22/200910/22/2009APART
DetailsForrest France
Overhead fire sprinkler rough-in inspection passed with the exception of two locations marked on plans in need of hangers/branchline restraint, cover is not approved until tenting/insulation is completed and inspected for cold cavity protection, be aware of light fixure obstructions that may develop depending on equipment installed, minor field mods. in pipe runs okayed due to 20% cushion in calcs, riser is not yet built.