INSP-Final Inspection | 12/16/2009 | 12/16/2009 | 12/16/2009 | P | PASS |
Forrest France
|
|
|
Fire alarm permit final approved.
|
INSP-Alarm Testing | 12/16/2009 | 12/16/2009 | 12/16/2009 | P | PASS |
Forrest France
|
|
|
Correction item field verified for compliance, inspection passed.
|
INSP-Final Inspection | 12/9/2009 | 12/11/2009 | 12/11/2009 | A | FAIL |
Forrest France
|
|
|
All correction notice items are finished with the exception of one HVAC unit which failed to shutdown upon smoke detection.
|
INSP-Final Inspection | 11/6/2009 | 11/6/2009 | 11/9/2009 | P | PART |
Forrest France
|
|
|
See notes dated 11/5.
|
INSP-Final Inspection | 11/2/2009 | 11/5/2009 | 11/5/2009 | A | PART |
Forrest France
|
|
|
Items needed for final include knox box installation, post signage at the door to the room containing the FACP, provide a lock at the circut breaker to the panel, post a map at the panel indicating locations of initiating devices and addresses/zones, one duct detector (#2) needs to be retested for unit shutdown as HVAC controls could not be initiated. See fire code review notes items # 21,22 and 23. Remainder of fire alarm work passed inspection and site testing.
|