INSP-Final Inspection | 7/29/2010 | 7/29/2010 | 7/30/2010 | P | PASS |
Troy Cobbley
|
|
|
Permit finaled
|
INSP-Final Inspection | 6/8/2010 | 6/9/2010 | 6/9/2010 | P | FAIL |
Troy Cobbley
|
|
|
The tamper switches tested ok. Still need the signage prior to a final sign off.
|
INSP-Sprinkler Rough-in/Hydro | 5/24/2010 | 5/26/2010 | 5/26/2010 | A | PASS |
Troy Cobbley
|
|
|
Jeff is looking for the original correction list. If all items have been met on that list then the remaining items are the signage as discussed and copies of the test papers.
|
INSP-Final Inspection | 5/24/2010 | 5/25/2010 | 5/24/2010 | A | CANC |
Troy Cobbley
|
|
|
We would like to perform this at 11:00 due to constraints with pipeline shutdowns. Inspection requested from web by: Jeff Packham Phone #: ###-#### Inspection cancelled from web by: Jeff Packham
|
INSP-Conference | 4/9/2010 | 4/9/2010 | 4/9/2010 | P | DONE |
Troy Cobbley
|
|
|
Me, Mark Sentenno and Tim Frost met with Jeff Pacham with Treasure Valley Fire and two representatives of Chevron, Lloyd and Steve and discussed outstanding issues from the last inspection. The tamper switches will be replace with devices that comply with NFPA 72, the pump and related electrical wiring needs to be above the water line (doors are ok for drainage). Tim is researching the required ventilation. The other items will be owner or fire sprinkler contractor supplied.
|
INSP-Sprinkler Rough-in/Hydro | 2/12/2010 | 2/12/2010 | 2/12/2010 | P | PART |
Forrest France
|
|
|
New overhead fire sprinkler system piping passed hydrostatic testing downstream of the riser control valve.
|
INSP-Final Inspection | 1/29/2010 | 2/9/2010 | 2/9/2010 | P | FAIL |
Troy Cobbley
|
|
|
Provide corrosion protection for the exterior sprinkler piping, provide ventilation per the review comments and nfpa 20, provide a floor drain per the review comments and nfpa 20, remove the old sprinkler piping, verify the nozzles are not plugged, provide complete testing for the entire scope of work (such as fire pump cert.), provide correct tamper switches (automatic resetting).
|