Permit Information
Permit NumberFIR09-00587
StatusFinaled
Name MOUNTAIN ALARM
Site Address 827 E PARK BLVD STE 100 & 120
Project NamePEAK BROADCASTING
Customer Number 
ePlanReview 
Description
This fire alarm permit is to add and relocate notification devices to meet spacing requirements of a new tenant area.

Associated building permit: BLD09-01337 (PEAK BROADCASTING - Morrison Foundation Building - STE# 100) Permit is to combine the two first floor tenants into a 9,765 square foot whole floor tenant and remove the interior unenclosed stair to isolate the second floor into two tenant spaces (suite 201 / 8,647 square feet and suite 200 / 1,362 square feet). Approval per approved plans on file. Work to include: [construction of interior non-bearing walls to create five offices, one storage room, a receptionist area, and a work room], demo existing unenclosed stairwell and infill with original const., relocating existing lighting, relocate existing ducts and diffusers, new doors and hardware, new accessible sales and service counter, and interior finishes in compliance with chapter 8 of the 2006 IBC. This building is fully fire sprinklered any alterations or modifications to the sprinkler system WILL REQUIRE A SEPARATE PERMIT and shall be installed per NFPA #13 as regulated by the fire department. *TLW**
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection11/17/200911/17/200911/17/2009APASS
DetailsForrest France
Fire alarm permit work finaled.
INSP-Final Inspection11/12/200911/13/200911/13/2009APART
DetailsForrest France
Noted correction items repaired, functional testing and signals sent completed satisfactory, need to provide accurate as-builts and NFPA record of completion forms prior to final approval.
INSP-Final Inspection11/9/200911/10/200911/10/2009ANR
DetailsForrest France
Per contractor sync issues are not yet resolved.
INSP-Final Inspection11/9/200911/9/200911/9/2009PCANC
DetailsForrest France
Chris Farnsworth Phone #: ###-#### Inspection cancelled from web by: Diane Turner
INSP-Final Inspection11/3/200911/3/200911/3/2009PFAIL
DetailsForrest France
Noted one overspaced notification device, one obstructed horn/strobe at the engineer room, one existing strobe is mounted too high, per contractor new and existing notification circut appliances are not in synchronization.