Permit NumberFIR09-00588
StatusFinaled
Name SIMPLEX GRINNELL
Site Address 125 E IDAHO ST
Project NameIDAHO PROFESSIONAL BLDG
Customer Number 
ePlanReview 
Description
This fire alarm permit is to add smoke detectors, a heat detector, a pull station, notification, and monitoring for existing HVAC units due to a tenant improvement. This permit scope also includes the addition of an extender panel to accommodate the new notification devices as well as the addition of cards to the existing FACP to accommodate the new initiating devices. There is an existing AES Wireless transmission panel installed under FIR09-00558.

Associated building permit: BLD09-01091 (ST. LUKES) (IDAHO PROFESSIONAL BLDG 3RD FLOOR) Remodel to the existing 6,797 sq. ft. space on the third floor of an existing building per approved plans. Work to include demolition within the surrounding perimeter walls in preparation for the remodel; construction of interior non-bearing walls to create offices, reception / waiting, work areas, break / locker / conference room, exam & procedure rooms; four fully accessible restrooms & accessible drinking fountains; modification of the electrical, mechanical, plumbing, fire suppression and alarm systems; add new interior finishes, cabinetry, doors and hardware. To install new main entry door & hardware at grade for accessibility compliance. NOTE: This building is fully sprinklered with sprinkler system used as substitution for 1-hour construction under the UBC in effect at time of construction. drs
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection3/4/20103/5/20103/5/2010APASS
DetailsForrest France
Correction items verified for completion, as-built plan accepted, fire alarm permit finaled.
INSP-Final Inspection3/2/20103/3/20103/3/2010APART
DetailsForrest France
Correction items include relocate duct detector at RTU 302, provide correct sample tubes per mfg. cut sheets for respective duct widths at all 8 DD, post an updated map at the panel per review comments, provide a lock and label at the breaker to the new nac, provide as-builts for field modifications including added notification appliances for the new exam room 340, stair 302, and revised operations matrix for duct detectors programed as alarm, contractor to check sync module for discrepancy between circuts N1:1- N1:2 and N1:3. Remainder of the scope of work passed inspection.
FIR-Aging Inspection1/4/20101/4/20101/4/2010 DONE
DetailsForrest France
Site work in progress, construction underway.