INSP-Final Inspection | 2/10/2010 | 2/10/2010 | 2/10/2010 | P | PASS |
Forrest France
|
|
|
Fire alarm permit final approved.
|
INSP-Final Inspection | 2/9/2010 | 2/9/2010 | 2/9/2010 | P | PART |
Forrest France
|
|
|
Correction notice items verified for completion, remainder of alarm work passed site testing. Final pending offsite monitoring check via permit FIR09-00740. Contractor to provide missing signage at the door to the FACP room.
|
INSP-Final Inspection | 2/5/2010 | 2/5/2010 | 2/9/2010 | P | NR |
Forrest France
|
|
|
Pending modifications per previous inspection- not ready 2/5 per phone call from contractor.
|
INSP-Final Inspection | 2/4/2010 | 2/4/2010 | 2/4/2010 | P | FAIL |
Forrest France
|
|
|
Smoke detectors at three locations are too close to HVAC diffusers, missing one SD address D1-13, HVAC units must shut down immediately upon duct smoke activation. Fire sprinkler riser supervision tested okay, five MP stations, battery trouble, open circuts, and notification circuts all passed functional testing. Offsite monitoring to be verified under project related FIR permit inspection. Plan resubmittals verified.
|