INSP-Final Inspection | 5/6/2010 | 5/7/2010 | 5/7/2010 | P | PASS |
Forrest France
|
|
|
Corrections field verified, fire sprinkler permit final approved.
|
INSP-Final Inspection | 5/4/2010 | 5/5/2010 | 5/5/2010 | P | FAIL |
Forrest France
|
|
|
Two pendent heads at the first floor living room are blocked by surface mounted ceiling obstructions, missing escutcheon at one sw head basement level, master bedroom 2nd pc. canopies need adjustment, delay at flow switch <5 sec.
|
INSP-Final Inspection | 4/1/2010 | 4/1/2010 | 4/1/2010 | P | PART |
Forrest France
|
|
|
Construction underway
|
INSP-Supply line flush | 1/27/2010 | 1/28/2010 | 2/1/2010 | P | PART |
Forrest France
|
|
|
Supply line flush okayed per site visit and activity notes 1/29.
|
INSP-Supply line flush | 1/28/2010 | 1/29/2010 | 1/29/2010 | A | PART |
Forrest France
|
|
|
Supply line flush completed acceptable.
|
INSP-Final Inspection | 1/14/2010 | 1/15/2010 | 1/15/2010 | A | PART |
Forrest France
|
|
|
Remainder of overhead rough-in okayed for cover at both basement and first floor levels.
|
INSP-Sprinkler Rough-in | 1/13/2010 | 1/14/2010 | 1/14/2010 | A | PART |
Forrest France
|
|
|
Overhead rough-in is satisfactory except as noted on plans-one area missing drops is incomplete, main level bedroom #2 head appears too close to a ceiling fan as marked on drawings, riser not yet tied in, discussed supply line flush, tenting is acceptable.
|