INSP-Final Inspection | 9/7/2010 | 9/8/2010 | 9/8/2010 | A | PASS |
Troy Cobbley
|
|
|
Permit finaled
|
INSP-Final Inspection | 9/1/2010 | 9/3/2010 | 9/3/2010 | A | FAIL |
Troy Cobbley
|
|
|
Provide approved map with all required information and mount at the facp.
|
INSP-Alarm Testing | 5/14/2010 | 5/14/2010 | 5/14/2010 | P | DONE |
Troy Cobbley
|
|
|
Fire sprinkler risers #2 and #3 inspected today. Flow switches and tamper switches functioned correctly. These items are not shown on the fire alarm plans and will need to be included when the plan modifications are submitted prior to a final sign off.
|
INSP-Alarm Testing | 4/20/2010 | 4/21/2010 | 4/20/2010 | A | CANC |
Troy Cobbley
|
|
|
If possible could we get before 8:00am. Nick is the contact his no. is ###-####. Thank you. Inspection requested from web by: Shawna Gates Phone #: ###-#### Inspection cancelled from web by: Shawna Gates
|
INSP-Alarm Testing | 4/19/2010 | 4/20/2010 | 4/19/2010 | A | CANC |
Troy Cobbley
|
|
|
Nick is the contact his no. is ###-####. Inspection requested from web by: Shawna Gates Phone #: ###-#### Inspection cancelled from web by: Shawna Gates
|
INSP-Alarm Testing | 4/15/2010 | 4/16/2010 | 4/15/2010 | A | CANC |
Troy Cobbley
|
|
|
Nick is the onsite contact his no. is ###-####. Thank you. Inspection requested from web by: Shawna Gates Phone #: ###-#### Inspection cancelled from web by: Shawna Gates
|
INSP-Alarm Testing | 3/23/2010 | 3/24/2010 | 3/24/2010 | A | PASS |
Troy Cobbley
|
|
|
The lobby area horn/strobes of phase 6 functioned correctly.
|
INSP-Alarm Testing | 3/22/2010 | 3/23/2010 | 3/23/2010 | A | PASS |
Troy Cobbley
|
|
|
The phase 8 existing fire alarm horns operated. We found that the new a/v's in the main lobby had not been inspected or connected to the NAC panel.
|
INSP-Alarm Testing | 12/3/2009 | 12/3/2009 | 12/3/2009 | P | DONE |
Troy Cobbley
|
|
|
Phase 4 fire alarm installation and testing is complete.
|
INSP-Final Inspection | 12/2/2009 | 12/3/2009 | 12/3/2009 | A | FAIL |
Troy Cobbley
|
|
|
This inspection is for phase 4. One additional horn/strobe needs to be installed as per the approved plans. Also horn only devices were not installed in the right hand corridor system of phase 4 as per the plans. Either re-install the horns or provide code compliant coverage through out the entire space served by the corridor system which includes the Lobby area.
|