Permit Information
Permit NumberFIR09-00641
StatusFinaled
Name ALARM STAR
Site Address 10139 W OVERLAND RD
Project NameSpring Creek - Bldg D
Customer Number 
ePlanReview 
Description
PLAN MODIFICATION: 2/26/10
This plan modification is to incorporate the previous review comments and redlines, as well as provide as-built conditions. Since the previous review, relays for access control and door holders have been added.


This fire alarm permit is to provide a new manual and automatic fire alarm system in a new building. Permit scope to include smoke detection, pull stations (as noted), heat detector, notification, and sprinkler system, hood suppression system, & HVAC monitoring.


Associated building permit: BLD09-00244 Spring Creek Overland - Senior Assisted-Living - Building D - Project consists of construction and finish of a 26,506 sq. ft., 42 sleeping unit, 50 bed, Senior Assisted Living Development with support facilities and associated site work, all per reviewed plans. To construct 18 one bedroom @ 552 sq. ft.; 12 Large Studio units @ 384 sq. ft.; 6 Small Studio Units @ 300 sq. ft.; and 6 Private HC units @ 227 sq. ft., six fully accessible units and 36 Type 'B' accessible units. drs DRH08-00246 CUP08-00010
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection3/1/20103/1/20103/2/2010PPASS
DetailsTroy Cobbley
Permit finaled
INSP-Alarm Testing2/22/20102/22/20102/22/2010PPART
DetailsTroy Cobbley
A temporary occupancy was given with Scott's permission until the as-built fire alarm plans have been reviewed, approved and any changes inspected. When this is done the permit can be finaled.
INSP-Alarm Testing2/19/20102/19/20102/19/2010PFAIL
DetailsTroy Cobbley
The testing and inspection is complete except for resubmittals showing all of the changes including wall mount a/v's and the additional common area smoke detectors/av's in the new "rehab" room. The door holder circuit and the hvac shutdown was repaired while I was on site.
INSP-Final Inspection2/18/20102/18/20102/18/2010PFAIL
DetailsTroy Cobbley
The FACP panel, phone line troubles, battery troubles, type 1 hood suppression system interconnection and the interconnections with the new fire alarm system passed. Also passed were the system smoke detectors located in the central wing. The system smoke detectors in the west wing did not function correctly due to one detector being smoked in a room activated the sounder base in a room across the hall. I let Micheal know that resubmittals will be required showing the additional door magnet interconnections.
INSP-Alarm Testing2/16/20102/16/20102/16/2010PCANC
DetailsTroy Cobbley
Cancelled per Michael or ###-#### Rand Phone #: ###-####