Description |
The Fire Sprinkler Scope of work consists of adding and relocating sprinklers to accommodate new wall and ceiling configuration. The existing system is a 6"x4"x2 ½" Grid designed for .495/2000 utilizing K=25.2 sprinklers. The new TI is predominantly light hazard except for a parking storage area, which is Ordinary Hazard Group I. The existing LO sprinklers are being used for the parking area. The remainder of the sprinklers are being changed to QR K=5.6 and K=11.2 (18'x18' spacing). The existing structure is steel bar joist. A new full height-demising wall is being added. The new wall required additional sprinklers due to spacing on the side opposite of the TI.
Vic Park Bldg 3: (Vanilla finish) Permit for minor tenant improvements to create a 6,012 sq. ft. tenant space in a 32,942 sq. ft. shell building with work to include the infill of on overhead door and man door, removal of two knock out panels (one for a overhead door and one for a man door), the construction of a 8" fuly grouted reinforced CMU tenant demizing wall to the roof deck and the construction of a truck ramp. This is a fully sprinklered building; any alterations to the sprinkler system will require a separate permit and shall comply with NFPA13 as regulated by Boise City Fire Department. All work to be done per the approved plans, plan review report, CZC09-00181 and any notations. The shell building was constructed under BLD07-00737. CDM
|