The Fire Sprinkler Scope of work consists of adding and relocating sprinklers to accommodate new wall and ceiling configuration. The existing system has a 4"x1 ½"x1 ¼" grid. However, the plans do not show the entire system. It appears an additional main may exist. The existing system was reported designed for 120sf with .20/1500. The new TI is 225sf with .15/1500. The existing water supply is reported as S=65, R=20, Q=2500
(BROWN MACKIE COLLEGE - SOUTHEAST CORNER OF BUILDING) This building is fully fire sprinklered for area increase. To create a 7,144 square foot tenant space within an existing 44,703 square foot, one story building. This tenant space will be an educational occupancy for students above the 12th grade. It will be a teaching facility for educational programs including veterinary technician and criminal justice. It will include classrooms, criminal justice labs, pet treatment, pet surgical lab, and pet boarding. There will be an X-ray machine and an oxygen storage room. Work is to include interior nonbearing walls, a nonrated corridor, 2 restrooms accessible to the disabled, 1 unisex restroom accessible to the disabled, movable pet kennels, a folding partition, interior doors, interior windows, millwork, and finishes. The work is required to comply with the approved drawings, with the plan review report, and with all applicable codes and ordinances. The fire sprinkler system is required to comply with NFPA 13 as regulated by the Fire Department. **CJW**
|