Permit NumberFIR09-00674
StatusFinaled
Name ALARMCO
Site Address 5383 W KENDALL ST
Project NameKENDALL CENTER-ID DPT. RECORDS
Customer Number 
ePlanReview 
Description
This fire alarm permit is to provide a new FACP for sprinkler system monitoring in an existing tenant space. An AES RF panel is being used to transmit signals in place of a DACT. Sprinkler system is partial for this tenant space only, not the entire building. Plans do not indicate HVAC. Notification is not part of this permit scope. Associated building permit: BLD10-00152 (Idaho Department of Administration) Only this tenant space is sprinklered. Application for inspection to determine requirements for issuance of a certificate of occupancy for an existing 3,500 square foot tenant space used for storage of files by Idaho State Records. Steel shelving 10 FEET IN HEIGHT WITH MAXIMUM STORAGE HEIGHT OF 12 FEET OR LESS, is being installed under separate permit, BLD10-00120. The sprinkler system for this tenant space was / is being installed under FIR09-00600. The rest of the building is not sprinklered. Plans from records on file are for the building, fiche #960249, building #3 constructed in 1978.Any modifications to sprinklered or alarm system required separate submittals & permits as regulated by fire dept. before work can commence. See attached checklist. drs
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection3/4/20103/5/20103/5/2010APASS
DetailsTroy Cobbley
Permit finaled
INSP-Final Inspection3/4/20103/4/20103/4/2010PFAIL
DetailsTroy Cobbley
Provide a map at the facp as discussed, provide corrected address at the monitoring station, provide as-builts that show the manual pull and smoke detector combined on zone 1, with zone 2 as a tamper, zone three as a PIV and zone 4 as the flow switch. Change out the submittal data sheet for the AES panel from a model 7750 to the 7788 which was actually installed. NetCon was a 5. All other items are passed.