Permit Information
Permit NumberFIR09-00681
StatusFinaled
Name SHILO AUTOMATIC SPRINKLER CO
Site Address 3882 N WOODY LN
Project Name36th St. Live-Work Unit #26
Customer Number 
ePlanReview 
Description
The Fire Sprinkler Scope of work consists of a new 13D system protecting a two-story live work unit. The system has a 1" supply and is equipped with a 1" meter. The 1¼" riser has a 1¼" backflow. The piping is CPVC except for below the backflow preventer.

Plan Mod Scope:
Change all piping on lower level from CPVC to Steel due to elimination of a ceiling.


(live/work unit 26) To construct a 2000 Sqft. two story, Live/Work unit (Townhouse) on a zero lot line. The First story includes a 756 Sqft. non-residential use, operated by the tenant and shall comply with section 419 of the 2007 International Building Code Supplement. The first story also has a 36 Sqft. covered porch, an 89 Sqft. covered patio, and a 464 Sqft. attached two-car garage. A maximum of five non-residential workers or employees are allowed to occupy the non-residential area at any one time. The second story includes a 1244 Sqft. two bedrooms, two bathrooms, dwelling unit with an 89 Sqft. balcony. The dwelling unit shall comply with the 2006 International Residential Code for a Single-family townhouse dwelling. This building shall conform to section 903.3.1.3 of the 2006 IBC. An automatic sprinkler system shall be installed throughout in accordance with NFPA 13D. All NFPA 13D systems shall be equipped with an alarm-initiating device commonly referred to as a flow switch, and an outside alarm-indicating device. A Fire Sprinkler Permit is required prior to beginning any fire sprinkler work. "This lot is within a Floodplain area. An elevation certificate is required to be submitted to and approved by Jim Wyllie, Public Works Department, prior to calling for a framing inspection." All work per the approved plans, engineering, plan review report, and alternate agreements on file. DRH07-00466, DRH08-00126, and CUP07-00121 per Planning and Zoning. **SRZ**
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection4/28/20104/29/20104/29/2010PPASS
DetailsTroy Cobbley
Permit finaled
INSP-Final Inspection4/26/20104/27/20104/27/2010PDONE
DetailsTroy Cobbley
Mike B is the contact. Thanks Inspection requested from web by: Stan Beus Phone #: ###-####

There were no approved plan on the job site. There was missing escutcheon and two sprinklers were blocked by exposed duct work.
INSP-Sprinkler Rough-in3/11/20103/11/20103/11/2010PPASS
DetailsTroy Cobbley
The piping changes have been addressed by tim frost and per mike a lintel is being installed to separate the shower from the restroom. Sprinkler piping can be covered.
INSP-Sprinkler Rough-in3/8/20103/9/20103/9/2010PFAIL
DetailsTroy Cobbley
Resubmittals are required due to pipe routing and sizing that differs from the approved plans. One pendant on the second floor needs to be relocated since it exceeds 8' from the kitchen wall. There is shadowing in the second floor bathroom. An additional head will be required or a lintel/soffit installed as discussed.