INSP-Final Inspection | 1/4/2010 | 1/4/2010 | 1/4/2010 | P | PASS |
Troy Cobbley
|
|
|
Permit finaled. The netcon rating was verified at 5 and all signals have been reverified.
|
INSP-Final Inspection | 12/24/2009 | 12/24/2009 | 12/24/2009 | P | NR |
Forrest France
|
|
|
Not ready for final per phone call from contractor.
|
INSP-Alarm Testing | 12/22/2009 | 12/23/2009 | 12/23/2009 | P | FAIL |
Stephanie L. Cobbley
|
|
|
(3:30pm 2nd inspection) Fire Alarm (NetCon) test failed. Rating reported a connectivity rating of 6. Minimum rating required per the manufacturers published installation instructions require a rating of 5 or less.
(11:30am 1st inspection) Fire Alarm inspection performed. At the time of this fire alarm inspection the building fire sprinkler system monitoring was verified by the central alarm monitoring facility. However, the Network Connectivity (NetCon) rating for the new AES transmitter component could not be verified by the field inspector because the applicant did not have in their possession the required tool to perform this test. The applicant agreed to return later in the afternoon, with the required tool, in order to perform the required (NetCon) test with the City field inspector. Final approval of this fire alarm permit is subject to satisfactory field inspection by the PDS/Fire inspector.
|