Permit Information
Permit NumberFIR09-00728
StatusFinaled
Name MOUNTAIN ALARM
Site Address 4770 N SHAMROCK AVE
Project NameGUARDIAN ANGELS DAYCARE
Customer Number 
ePlanReview 
Description
5-27-10: PLAN MODIFICATION
This plan modification includes adding/relocating devices due to an adjustment of the originally submitted floor plan as well as incorporate redlines and review comments from the review dated 1-21-10.

1-21-10:This fire alarm permit is to provide a new manual and automatic fire alarm system for a re-built building. System to include smoke detection, pull stations, notification, and monitoring for HVAC. This building is not sprinklered. The fire alarm system signals report via an AES RF radio to the central station.
Associated building permit: BLD09-00323 (GUARDIAN ANGELS DAYCARE) 10-26-09 PLAN MODIFICATION ADDING FLOOR AREA; CREATE ADDITIONAL ROOM & RESTROOM; RELOCATING AND ADDING INTERIOR SUPPORT ROOMS; ADD EXTERIOR DOOR AND WINDOW; REDUCING OTHER WINDOW AREA; CHANGE METAL ROOF TO ARCHITECTURAL SHINGLES IN SOME LOCATIONS; MODIFY ENERGY CODE LIGHTING & ENVELOPE; MODIFY KITCHEN LAYOUT; ADD SMOKE ALARM MODIFICATION AND PROVIDE PREVIOUSLY DEFERRED SYUBMITTAL ITEMS. DRS To construct and finish a new 5,800 sq. ft. daycare facility on portions of a new and existing foundation with a 330 sq. ft. mezzanine as part of the floor area. Interior bearing and non-bearing walls to create common areas and classroom/activity rooms. Building has a fire alarm system. drs
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection6/7/20106/8/20106/8/2010PPASS
DetailsTroy Cobbley
Permit finaled.
INSP-Final Inspection6/3/20106/4/20106/4/2010PFAIL
DetailsTroy Cobbley
The manual pull stations have been corrected. The gas still has not been turned on to the hvac units so they could not be tested and the fire alarm panel is showing a "COMM 1" trouble.
INSP-Final Inspection6/1/20106/2/20106/2/2010PFAIL
DetailsTroy Cobbley
All of the previous corrections have been made. All of the smoke detectors tested and reported as per plan. The manual pull stations tested ok but did not report per plan. Also the heat detector 001 in the closet kept reporting as a trouble even though it was not being tested. Also a Com trouble kept comming up. The duct smoke detectors could not be tested since the gas has not been turned on to the hvac units.
INSP-Final Inspection6/1/20106/1/20106/2/2010PCANC
DetailsTroy Cobbley
Cancelled due to time constraints. Rescheduled for tomorrow.
INSP-Final Inspection4/28/20104/28/20104/28/2010PFAIL
DetailsTroy Cobbley
Plans need to be resubmitted showing the wall layout changes which will require additional notification device/devices. Several smoke and heat detectors were located less than 3' from supply registers. One strobe on the second level was not set at the correct candella and was corrected while on site. Voltage drops were verified for both of the notification circuits and both circuits checked out ok. The Netcon was verified at a 5 multiple times. All other notication device locations are approved except as noted above due to wall changes.
INSP-Conference4/6/20104/7/20104/7/2010PDONE
DetailsTroy Cobbley
This conference was to discuss the placement of a manual pull station at the center east exit. The request was to place the pull station on a cabinet. That was declined. It was decided that the pull station would be place on the left side door frame, next to the refrigerator. Mounting height was also discussed.
INSP-Conference4/6/20104/8/20104/6/2010PCANC
DetailsTroy Cobbley
Bret Anderson- our office is in Nampa so please give us time to arrive on time to meet you. We will also be calling the contractor to be included in the meeting. Inspection requested from web by: Diane Turner Phone #: ###-#### Inspection cancelled from web by: Diane Turner