INSP-Final Inspection | 3/11/2011 | 3/11/2011 | 3/15/2011 | P | PASS |
Forrest France
|
|
|
Fire alarm permit finaled.
|
INSP-Alarm Testing | 3/10/2011 | 3/10/2011 | 3/15/2011 | P | PART |
Forrest France
|
|
|
Acceptance testing continued with corrections noted.
|
INSP-Alarm Testing | 3/11/2011 | 3/11/2011 | 3/15/2011 | A | PART |
Forrest France
|
|
|
Acceptance testing continued- see plans for annotations pertaining. Corrections underway.
|
INSP-Alarm Testing | 3/3/2011 | 3/3/2011 | 3/4/2011 | A | PART |
Forrest France
|
|
|
Dan phone #: ###-####
|
INSP-Final Inspection | 2/18/2011 | 3/2/2011 | 3/2/2011 | A | PART |
Forrest France
|
|
|
Tested fire alarm notification and initiating devices on the 2nd -7th floor tower levels, verified previous correction items are finished, booster 2 nac 3 first floor is not functional, add TS at the antifreeze loop to the points map, adjust cd and spacing at area D 2nd and 3rd floors as noted.
|
INSP-Conference | 3/1/2011 | 3/1/2011 | 3/1/2011 | P | DONE |
Forrest France
|
|
|
|
FIR-Aging Inspection | 1/10/2011 | 1/10/2011 | 1/10/2011 | | DONE |
Forrest France
|
|
|
Corrections underway.
|
INSP-Conference | 11/8/2010 | 11/8/2010 | 11/8/2010 | A | DONE |
Forrest France
|
|
|
Regarding fire alarm work in progress.
|
INSP-Conference | 10/19/2010 | 10/19/2010 | 10/20/2010 | A | DONE |
Forrest France
|
|
|
Regarding work in progress and schedule for next site visit and reinspection.
|
INSP-Alarm Testing | 8/26/2010 | 9/7/2010 | 9/15/2010 | P | FAIL |
Forrest France
|
|
|
Noted several items on initial walkthough in need of amendment- ref. plans and review notes for conditions and locations. Note: exisitng yard PIV must be provided with electronic tamper supervision.
|
INSP-Conference | 8/31/2010 | 8/31/2010 | 9/1/2010 | P | DONE |
Forrest France
|
|
|
Regarding site inspection schedule for acceptance testing.
|
INSP-Alarm Testing | 7/14/2010 | 8/6/2010 | 8/6/2010 | A | CANC |
Forrest France
|
|
|
Dan ###-####
|
FIR-Aging Inspection | 7/14/2010 | 7/14/2010 | 7/15/2010 | | DONE |
Forrest France
|
|
|
Site work in progress.
|