Permit Information
Permit NumberFIR10-00006
StatusFinaled
Name STATEFIRE DC SPECIALITIES
Site Address 1800 W FAIRVIEW AVE
Project NameRED LION DOWN TOWNER UPGRADE
Customer Number 
ePlanReview 
Description
This fire alarm permit is to replace the existing fire alarm panel with new to accommodate an elevator upgrade (all elevators). The building will be upgraded to accommodate current visual notification requirements due to the FACP replacement. Devices for elevator recall functions shall be new and addressable, other existing devices to remain as circuited, with the existing zones being re-landed on the new FACP. This fire alarm control panel is addressable and conventional. HVAC functions have not been shown on the plans. There is no associated building permit.

NOTE TO INSPECTOR: An early start agreement has been approved for this project. The existing initiating devices are to remain as-is unless those devices are replaced and/or relocated; in which case the devices shall then be required to meet current code mounting and spacing requirements.
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection3/11/20113/11/20113/15/2011PPASS
DetailsForrest France
Fire alarm permit finaled.
INSP-Alarm Testing3/10/20113/10/20113/15/2011PPART
DetailsForrest France
Acceptance testing continued with corrections noted.
INSP-Alarm Testing3/11/20113/11/20113/15/2011APART
DetailsForrest France
Acceptance testing continued- see plans for annotations pertaining. Corrections underway.
INSP-Alarm Testing3/3/20113/3/20113/4/2011APART
DetailsForrest France
Dan phone #: ###-####
INSP-Final Inspection2/18/20113/2/20113/2/2011APART
DetailsForrest France
Tested fire alarm notification and initiating devices on the 2nd -7th floor tower levels, verified previous correction items are finished, booster 2 nac 3 first floor is not functional, add TS at the antifreeze loop to the points map, adjust cd and spacing at area D 2nd and 3rd floors as noted.
INSP-Conference3/1/20113/1/20113/1/2011PDONE
DetailsForrest France
FIR-Aging Inspection1/10/20111/10/20111/10/2011 DONE
DetailsForrest France
Corrections underway.
INSP-Conference11/8/201011/8/201011/8/2010ADONE
DetailsForrest France
Regarding fire alarm work in progress.
INSP-Conference10/19/201010/19/201010/20/2010ADONE
DetailsForrest France
Regarding work in progress and schedule for next site visit and reinspection.
INSP-Alarm Testing8/26/20109/7/20109/15/2010PFAIL
DetailsForrest France
Noted several items on initial walkthough in need of amendment- ref. plans and review notes for conditions and locations. Note: exisitng yard PIV must be provided with electronic tamper supervision.
INSP-Conference8/31/20108/31/20109/1/2010PDONE
DetailsForrest France
Regarding site inspection schedule for acceptance testing.
INSP-Alarm Testing7/14/20108/6/20108/6/2010ACANC
DetailsForrest France
Dan ###-####
FIR-Aging Inspection7/14/20107/14/20107/15/2010 DONE
DetailsForrest France
Site work in progress.