Permit Information
Permit NumberFIR10-00014
StatusFinaled
Name AMERICAN FIRE PROTECTION LLC
Site Address 130 N MILWAUKEE ST
Project NamePETSMART
Customer Number 
ePlanReview 
Description
The Fire Sprinkler Scope of work consists of adding sprinklers to a new over build area and part of a canopy. A portion of the canopy is existing and already has fire protection. The intention is for the entire canopy to have fire protection. Combustibles are NOT to be stored or handled below the canopy due to insufficient density. Therefore, sidewalk sales are not permitted. There will be above and below protection on the new portion of the canopy.

(PETSMART TENANT IMPROVEMENT) This building is required to be fire sprinklered for building area increase. To construct interior tenant improvements within a new building shell for a pet store. This tenant space will be used for retail sales, pet salon, pet medical treatment, and pet boarding. The building shell was constructed under permit BLD09-01007. Work is to include interior nonbearing walls, interior doors, and interior windows, 2 restrooms accessible to the disabled, suspended acoustical ceilings, millwork, and finishes. The work is required to comply with the approved drawings, with the plan review report, and with all applicable codes and ordinances. The fire sprinkler system is required to comply with NFPA 13 as regulated by the Fire Department. A separate permit is required for high-rack storage. **CJW**
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection4/28/20104/29/20104/29/2010PPASS
DetailsTroy Cobbley
Permit finaled
INSP-Final Inspection4/22/20104/23/20104/23/2010ACANC
DetailsTroy Cobbley
ken Phone #: ###-####
INSP-Final Inspection4/14/20104/14/20104/14/2010PFAIL
DetailsTroy Cobbley
Permit will be ready to final when a fire alarm permit has been submitted for the new butterfly valve to be connected to the existing fire alarm system. I let the ken with American Fire and the PetsMart job superintendant that I would not final their permits until a fire alarm permit had been issued for this additional valve. This is due to the canopy permit, which this valve controls, being associated with the PetsMart permit.
INSP-Sprinkler Rough-in3/25/20103/26/20103/26/2010APASS
DetailsTroy Cobbley
The sprinkler piping as marked on the plans can be covered. The through bolts for the earth quake bracing have been addressed.
INSP-Sprinkler Rough-in3/24/20103/25/20103/25/2010APART
DetailsTroy Cobbley
The sprinkler piping rough-in is ok except for the lag bolts on the earthquake bracing attachments need to be changed to through bolts with the correct length and blocking as discussed. Could not make it back for a re-inspection/cover approval so Ken is scheduling for tomorrow morning.