Permit Number | FIR10-00023 |
Status | Finaled |
Name |
ALARMCO
|
Site Address |
805 W FRANKLIN ST
|
Project Name | Franklin Plaza |
Customer Number | |
ePlanReview | |
Description |
This quick permit is to relocate an existing notification device and provide a new one in a conference room due to a tenant improvement. Approval is subject to field measurement of the EOL voltage drop. The voltage drop calculations are based on a 10% drop, therefore the minimum acceptable voltage is 21.6V with the AC power off. Devices to be mounted per 2007 NFPA 72 mounting and spacing requirements. There are no written comments. Associated building permit: BLD09-02003 (CRADLEPOINT - 2ND & 4TH FLOORS) 12/8/09 - PLAN MODIFICATION FOR 2ND & 4TH FLOORS. CHANGE ROOM LOCATIONS AND SIZES, RELOCATE LIGHT FIXTURES AND CONTROLS. RELOCATE EXIT SIGN AT SECOND FLOOR TO BE IN FRONT OF NEW VESTIBULE DOORS, CONSTRUCT NEW FUTURE EXIT VESTIBULE ON SECOND FLOOR. ORIGINAL CODE PLAN REVIEWS AND RED-LINED NOTES ON ORIGINAL PLANS ARE STILL APPLICABLE TO THIS PERMIT. DRS NOTE:1st floor T.I. will be under separate permit. This building is fully sprinklered to substitute for 1-hour construction. Construct interior non-bearing walls to create private offices, open work areas, conference rooms and support areas; upgrade electrical, mechanical, sprinkler and alarm systems; and interior floor and wall finishes. Upgrade of stairs enclosures for code compliance will be under separate permit, BLD09-02173. drs
|