Permit Information
Permit NumberFIR10-00028
StatusFinaled
Name JBL FIRE PROTECTION LLC
Site Address 11818 W JOPLIN RD
Project NameWWTP Central Lab Addition
Customer Number 
ePlanReview 
Description
The Fire Sprinkler Scope of work consists of approximately 200'± 6" DI piping with associated fittings and thrust blocks. A new connection will made to the existing 4" riser. A new tree system will protect the new addition. The detection/releasing portion of the preaction system is under permit FIR10-00144

Plan Mod Scope:
The system piping arrangement was completely redesigned. It is now a double tree system with a 4" and 3" main.

Boise Public Works- West Boise Central Lab - Metals Lab Addition - To construct a 3,675 square foot, one story, wood framed addition on the west end of the existing West Boise Central Laboratory building and to do a small remodel within the existing building between grid lines 3 & 4 and B & D. This addition will include two new Metals Instruments Rooms, two new Preparation Rooms and two new Acid Wash Rooms, a new Mechanical Room, a new AWN Room and new entry. This addition will also have a five-foot high mechanical attic.
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection1/13/20111/14/20111/14/2011APASS
DetailsTroy Cobbley
permit finaled.
INSP-Final Inspection1/13/20111/13/20111/13/2011PCANC
DetailsTroy Cobbley
Canceled due to time constraints and Micron plan review
FIR-Aging Inspection1/3/20111/3/20111/10/2011 NR
DetailsTroy Cobbley
work is in progress
INSP-Sprinkler Rough-in11/2/201011/3/201011/3/2010PPASS
DetailsTroy Cobbley
The 24 hour air test passed
INSP-Sprinkler Rough-in11/1/201011/2/201011/2/2010APASS
DetailsTroy Cobbley
24 hr air test inspection started at 9:30 am with 46psi on the guage.
INSP-Sprinkler Rough-in/Hydro11/1/201011/1/201011/1/2010PPASS
DetailsTroy Cobbley
Overhead hydro test passed
INSP-Sprinkler Rough-in8/25/20108/25/20108/25/2010PPASS
DetailsTroy Cobbley
Above ground hydro test passed.
INSP-Sprinkler Rough-in/Hydro8/24/20108/25/20108/25/2010AFAIL
DetailsTroy Cobbley
Above ground hydro test failed. Earthquaking has been corrected and the FDC piping has been installed. Phone #: ###-####
INSP-Sprinkler Rough-in8/6/20108/6/20108/6/2010PPASS
DetailsTroy Cobbley
The rough-in inspection passed except for the earthquake bracing and the rerouted fire dept connection piping.