Permit Information
Permit NumberFIR10-00049
StatusFinaled
Name MOUNTAIN ALARM
Site Address 7235 W BETHEL ST
Project NameFarmer Brothers Coffee
Customer Number 
ePlanReview 
Description
This fire alarm permit is to provide a new sprinkler monitoring system in an existing building due to a tenant improvement. Notification is not part of this permit scope. HVAC functions were not indicated, therefore will require a re-submittal or separate permit if duct detectors are required/installed. An upgrade agreement exists for this address but does not appear to have any impact on the fire alarm at this time. For further details, see the upgrade agreement document attached to BLD09-02253.

Associated building permit: BLD09-02253 (FARMERS BROTHERS COFFEE) Permit is to remodel an existing 8,032 square foot office / warehouse building. UPGRADE AGREEMENT APPROVED FOR THIS BUILDING - agreement is attached to this case. Approval contingent upon adhering to the approved plans on file, attached engineering, and CZC09-00222. Work to include: [construction of interior non-bearing walls to create two fully accessible bathrooms, a new managers office, a fire sprinkler riser room, and to isolate off common area], installation of new accessible bathroom fixtures, installation of new hand sink, installation of new exterior landing, installation of new exterior loading ramp, installation of new opening in tilt-up wall, and finishes in compliance with chapter 8 of the 2006 IBC. This building is to be fully fire sprinklered per NFPA #13 as regulated by the fire department to comply with area requirements. Racking that exceeds 8 ft. in height requires a separate Building Permit be submitted and approved before installation (Racking permit # BLD09-02212). UPGRADE AGREEMENT APPROVED FOR THIS BUILDING - agreement is attached to this case. **TLW**
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection3/17/20103/19/20103/19/2010APASS
DetailsForrest France
Correction items revised, re-testing completed acceptable, as-builts recieved, fire alarm permit finaled.
INSP-Final Inspection3/18/20103/18/20103/18/2010PFAIL
DetailsTroy Cobbley
Trouble signals did not annuciate at the facp as required, battery was not a 8ah, as-builts reflecting the additional flow switch and the two additional tamper switches. Also the order in which the devices were tested was not reflected in the order that the central station received them. Electrician was going to provide the lock for the dedicated circuit. I let Doug know that signage would be required for the riser room/facp room door.