INSP-Final Inspection | 7/2/2010 | 7/6/2010 | 7/6/2010 | A | PASS |
Forrest France
|
|
|
Notification and voice evac circuts and appliances tested satisfactory, verified plan resubmittals for field modifications, corrections per last site visit finished. Fire alarm permit finaled.
|
INSP-Final Inspection | 6/14/2010 | 6/21/2010 | 6/18/2010 | A | CANC |
Forrest France
|
|
|
Call Lee ###-#### Inspection requested from web by: Mike Brown Phone #: ###-#### Inspection cancelled from web by: Mike Brown
|
INSP-Final Inspection | 5/28/2010 | 6/2/2010 | 6/2/2010 | A | FAIL |
Forrest France
|
|
|
Items not repaired and included on the original inspection correction list include the duct detector at "Taters", missing signage at the door to the FACP room, sprinkler tamper switch must report as a supervisory condition. Also noted a trouble on the panel at one beam detector, overspaced and missing notification at the mechanical mezzanine, walkthrough completed for area B. Attempted an expedited test of the building alarm notification circuts by providing an additional inspector on site- test failed due to non-functional voice evacuation speakers at the main convention hall. A re-inspection fee will apply to the next site visit, see permit conditions for details.
|
INSP-Final Inspection | 5/27/2010 | 5/28/2010 | 5/27/2010 | A | DEFR |
Forrest France
|
|
|
Mike Phone #: ###-#### Note: request intended for a different date per phone conversation.
|
INSP-Final Inspection | 5/17/2010 | 5/24/2010 | 5/25/2010 | A | FAIL |
Forrest France
|
|
|
Correction items for areas inspected to date include; HVAC duct smoke detector at address L2-S29 in concessions room 210 "Perch" failed to initiate unit shut down- plan sheet F.A.2.1, duct smoke detector address L1-S29 in "Tators" failed to shut down HVAC unit, missing tamper switch and monitor module at the outside control valve for the fire sprinkler system- F.A. 2.3/2.0, missing one notification appliance at exhibit hall 200- sheet F.A.2.5, post signage at the door to the FACP room per review notes, notification devices have been changed from wall mount to ceiling mount at the restrooms F.A.2.5, incorrect cd setting at lockers 179, minor adjustments to as-built plans discussed, need clarification of room use at the "business center" area D as is lacking notification. Items inspected include kitchen hood monitoring, fire sprinkler riser supervision, heat detectors, manual pull station, area smoke detection at the basement, all duct detectors, door holds, walkthrough regarding notification appliance locations for areas A, C and D.
|