Permit Information
Permit NumberFIR10-00072
StatusFinaled
Name CURTIS FIRE SPRINKLER SERVICE INC
Site Address 10464 W GARVERDALE CT
Project NameCENTER FOR SPIRITUAL LIVING
Customer Number 
ePlanReview 
Description
Fire Work Scope:

The Fire Sprinkler Scope of work consists of adding fire protection to an existing wood frame structure. The wet system is designed as a loop. There is an unsprinklered crawl space and stage. Most of the system has above and below protection.

(CENTER FOR SPIRITUAL LIVING) This building will be fully fire sprinklered for the occupant load in the fire area. To convert an existing 7,108 square foot office building (B Occupancy) to a church (A-3 Occupancy). Nonstructural work includes 2 restrooms accessible to the disabled, an interior ramp accessible to the disabled, interior nonbearing walls, interior doors, interior windows, exterior windows, and finishes. Structural work includes a new roof structure, bearing walls, beams, columns, headers, shear walls, joists, concrete footings, etc. The work is required to comply with the approved drawings, with the plan review report, with the structural design, and with all applicable codes and standards. The new fire sprinkler system is required to comply with NFPA 13 as regulated by the Fire Department. Interior nonstructural demolition was done under permit BLD10-00038. Planning approvals done under CUP09-00054, DRH09-00208, & DRH09-00281. **CJW**

________________________________________

Notice:

The building permit has not been issued at this time. The building department may determine that changes are required to the building plans in order to comply with the code. These changes may affect the sprinkler system. The sprinkler contractor will be required to make all necessary changes that may be required. Therefore, if the sprinkler contractor chooses to proceed without an issued building permit; they will do so on their own cognizance.
" 8/10/2010 The notice above no longer pertains since the permit was issued 06-15-10.

________________________________________


Plan Mod Scope of Work:

Changed four upright sprinklers to sidewall sprinklers per the owners request in the high area of the sanctuary.
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection3/29/20113/30/20113/30/2011APASS
DetailsTroy Cobbley
permit finaled
FIR-Aging Inspection3/29/20113/29/20113/30/2011 PASS
DetailsTroy Cobbley
INSP-Final Inspection1/27/20111/27/20111/27/2011PPART
DetailsTim Frost
This inspection was called in under the wrong permit BLD10-00114.

The exterior canopy was inspected. The canopy is completely filled with non-combustible insulation. I gave then the ok to cover the canopy with hardy board. Therefore no sprinkler was required.
INSP-Final Inspection12/8/201012/8/201012/8/2010PPART
DetailsTroy Cobbley
A temporary occupancy was given, with Scott's permission, until the front entry canopy is complete and the additional fire sprinkler is installed.
INSP-Final Inspection12/2/201012/3/201012/3/2010AFAIL
DetailsTroy Cobbley
Need to perform a job walk through and verify there are no head obstructions, need all of the final items at the riser such as backflow certification, head box, stickers...ect. Also noted that a pendant head was installed in the electrical room but a ceiling had not been installed.
INSP-Supply line flush12/2/201012/3/201012/3/2010APASS
DetailsTroy Cobbley
supply line flush passed.
INSP-Sprinkler Rough-in12/2/201012/3/201012/3/2010APASS
DetailsTroy Cobbley
The underground flush passed and the forward flush test of the backflow preventor passed.
INSP-Sprinkler Rough-in/Hydro12/2/201012/2/201012/2/2010PPASS
DetailsTroy Cobbley
The overhead hydro passed.
INSP-Sprinkler Rough-in/Hydro10/19/201010/20/201010/20/2010APASS
DetailsTroy Cobbley
The under ground hydro passed. No flush was performed.
INSP-Sprinkler Rough-in10/14/201010/15/201010/15/2010APASS
DetailsTroy Cobbley
The underground supply piping is ok to cover.
INSP-Sprinkler Rough-in8/25/20108/25/20108/25/2010PPASS
DetailsTroy Cobbley
The sprinkler piping in the high ceiling area, as discussed, can be covered.
INSP-Sprinkler Rough-in/Hydro8/19/20108/19/20108/19/2010PPASS
DetailsTroy Cobbley
Piping rough-in passed except for the two clouded areas marked on the plan in red where the piping has not been installed yet. Also one upright head is blocked by truss web members and is to be relocated as discussed. As-built plans will be required showing the piping routing changes. A hydro test was not performed since the upright needs relocated and none of the permanant sprinkler pendants/sidewalls have been installed. Branch line restraints have not been installed and the longitudinal earthquake bracing has not been installed. The insulation will be required to be installed at the deck since the upright sprinkler heads are located too far below the wood deck.
FIR-Aging Inspection7/9/20107/9/20107/9/2010 NR
DetailsTroy Cobbley
Work is in progress