INSP-Final Inspection | 7/30/2010 | 8/2/2010 | 8/3/2010 | P | PASS |
Forrest France
|
|
|
Corrections verified, final walkthrough and acceptance testing passed. Permit finaled.
|
INSP-Sprinkler Rough-in | 7/13/2010 | 7/13/2010 | 7/13/2010 | A | PART |
Forrest France
|
|
|
Ref. inspection notes and correction list 6/30.
|
INSP-Sprinkler Rough-in/Hydro | 7/1/2010 | 7/2/2010 | 7/2/2010 | P | PART |
Forrest France
|
|
|
Concluded satisfactory 24hr. air test for the new dry system per NFPA 13.
|
INSP-Sprinkler Rough-in/Hydro | 7/1/2010 | 7/1/2010 | 7/1/2010 | P | PART |
Forrest France
|
|
|
Begin 24 hour pneumatic test for the new dry system at 1:00PM @ 42psig.
|
INSP-Sprinkler Rough-in | 6/30/2010 | 6/30/2010 | 6/30/2010 | P | FAIL |
Forrest France
|
|
|
Missing one lateral seismic brace at the south end of the dry system main, shadowing at one office area, welded 2" outlets on the dry system mains serving branchlines at the exterior canopy at some locations are not properly graded, noted one dry pendent at the main entry has been added. See stamped plans for annotations.
|
INSP-Sprinkler Rough-in/Hydro | 6/29/2010 | 6/30/2010 | 6/30/2010 | A | PART |
Forrest France
|
|
|
Overhead hydrostatic test for both the wet and dry systems completed satisfactory.
|
INSP-Sprinkler Rough-in/Hydro | 6/28/2010 | 6/28/2010 | 6/28/2010 | P | DEFR |
Forrest France
|
|
|
john Phone #: ###-####
|