Information based on query as of Friday, July 5, 2024.
Permit Information
Permit NumberFIR10-00097
StatusFinaled
Name CURTIS FIRE SPRINKLER SERVICE INC
Site Address 1002 S VISTA AVE
Project NameVISTA VILLAGE SHOPPING CENTER
Customer Number 
ePlanReview 
Description
Quick Permit
Relocate, plug and add 6 sprinklers to accommodate new wall and ceiling configurtaion

(CERAMICA) The North wall of this tenant space is required to be a 2-hr fire wall. This building is fire sprinklered. To remodel an existing tenant space for a new retail sales pottery shop. Floor area from this tenant space and from an adjacent tenant space will be used to create a 241 square foot restroom core that will serve both tenant spaces. This tenant space will have a floor area of about 1,941 square feet. Work is to include interior nonbearing walls, interior doors, accessible high and low drinking fountains, and finishes. Both restrooms within the restroom core are required to be accessible to the disabled as defined by current standards. The work is required to comply with the approved drawings, with the plan review report, and with all applicable codes and ordinances. The fire sprinkler system is required to comply with NFPA 13 as regulated by the Fire Department. **CJW**
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection3/24/20103/24/20103/24/2010PPASS
DetailsForrest France
Fire sprinkler permit work passed final inspection, one existing "loaded" pendent adjacent to an HVAC diffuser cleaned while on site. Permit finaled.
INSP-Sprinkler Rough-in3/11/20103/11/20103/11/2010PPASS
DetailsTroy Cobbley
Sprinkler piping can be covered. Three pendants located at the kilns have not been changed to a higher temperature yet.