Permit Information
Permit NumberFIR10-00098
StatusFinaled
Name FIRE SENTRY SYSTEMS
Site Address 720 PARK BLVD Unit: 200
Project NameBMC WEST AT MK CENTRAL PLAZA 2
Customer Number 
ePlanReview 
Description
Scope
6-29-10 PLAN MODIFICATION:
This plan modification is to implement field changes as well as items from the original review.

3-15-10:
This fire alarm permit is to extend the existing fire alarm system into the new tenant space. This permit scope includes notification (voice evacuation), a new remote power supply to accommodate the visuals, and a smoke detector (non-required above the remote power supply). All new speakers are tapped at ΒΌ watt.

Associated building permit: BLD10-00338 (BMC SELECT - Washington Group Plaza - Ste# 200) Permit is to remodel an existing 25,348 square foot tenant space to accommodate the tenant's needs. Approval contingent upon adhering to the approved plans on file and obtaining the necessary Fire Alarm and Fire Sprinkler permits. Work to include: demolition of multiple enclosed offices to create more open office area, construction of interior non-bearing walls to create four new enclosed offices, installation of new accessible door hardware, installation of new doors and sidelights, and finishes in compliance with chapter 8 of the 2006 IBC. This building is fully fire sprinklered any alterations or modifications to the sprinkler system WILL REQUIRE A SEPARATE PERMIT and shall be installed per NFPA #13 as regulated by the fire department. Racking that exceeds 8 ft. in height requires a separate Building Permit be submitted and approved before installation. **TLW**
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection7/23/20107/23/20107/23/2010PPASS
DetailsForrest France
Fire alarm permit final approved.
INSP-Alarm Testing7/15/20107/16/20107/16/2010PPASS
DetailsTroy Cobbley
Permit finaled. EOL was verified
INSP-Final Inspection6/8/20106/10/20106/10/2010PFAIL
DetailsForrest France
Missing notification at one conference room, one area lacks sufficient visual coverage, need to verify mag locks at the main entry release on fire alarm, RR coverage, and audibility at two storage rooms during the functional test as discussed. Noted one overspaced 75cd appliance at the SE corner.
INSP-Final Inspection6/2/20106/4/20106/4/2010PCANC
DetailsTroy Cobbley
Per Josh this inspection will be rescheduled for later since his and I's schedules are not going to work out.