INSP-Final Inspection | 8/30/2011 | 9/1/2011 | 9/1/2011 | A | PASS |
Forrest France
|
|
|
Noted correction items finished. Fire alarm permit finaled.
|
INSP-Final Inspection | 7/29/2011 | 7/29/2011 | 7/29/2011 | P | PART |
Forrest France
|
|
|
Remainder of correction items include; repair one non-functional H/S at the womens locker room sauna, repair notification device at the first floor family restroom, adjust cd setting at one appliance in the basement level womens locker room. Need to verify EOL voltage and reverify notification functionality at the cardio area.
|
INSP-Conference | 7/27/2011 | 7/27/2011 | 7/27/2011 | A | DONE |
Forrest France
|
|
|
Zach phone #: ###-#### Regarding corrections and final inspection schedule.
|
INSP-Final Inspection | 7/20/2011 | 7/21/2011 | 7/22/2011 | A | FAIL |
Forrest France
|
|
|
Items noted during notification circut testing include sync issues at the basement level, various non-functional devices on the 1st floor, insufficient EOL voltage as measured, missing tone cycle preceeding and following the voice message, audibility at some areas such as the gym, spin, fitness, cardio and weight rooms do not appear sufficient.
|
INSP-Alarm Testing | 7/11/2011 | 7/11/2011 | 7/11/2011 | A | PART |
Forrest France
|
|
|
Ref. stamped plan set for annotations regarding devices tested to date.
|
INSP-Alarm Testing | 7/7/2011 | 7/7/2011 | 7/8/2011 | P | PART |
Forrest France
|
|
|
Completed elevator device testing, SD at nac's and FACP, reviewed changes and adjustments to date, discussed items remaining including AC power light at the panel, guards at gym appliances, signage at doors to the FACP, as-builts/map, and notification testing schedule.
|
INSP-Alarm Testing | 6/27/2011 | 6/28/2011 | 6/28/2011 | A | PART |
Forrest France
|
|
|
MP stations tested satisfactory.
|
INSP-Alarm Testing | 6/27/2011 | 6/27/2011 | 6/28/2011 | A | PART |
Forrest France
|
|
|
Remainder of duct detectors tested okay.
|
INSP-Final Inspection | 6/20/2011 | 6/23/2011 | 6/24/2011 | P | PART |
Forrest France
|
|
|
Completed testing of ID and DD at the first, second and third floors.
|
INSP-Conference | 6/6/2011 | 6/6/2011 | 6/6/2011 | P | DONE |
Forrest France
|
|
|
Regarding inspection schedule.
|
INSP-Alarm Testing | 5/25/2011 | 5/26/2011 | 5/26/2011 | A | PART |
Forrest France
|
|
|
Completed testing of ID and DD devices at the basement levels. Noted tamper valve at the elevator machine room to be monitored, as-builts to reflect deleted and added devices, dampers have been repaired and verified for functionality. Previously noted correction items underway, some are finished. Ref. plan set for annotations.
|
INSP-Alarm Testing | 5/25/2011 | 5/25/2011 | 5/25/2011 | A | PART |
Forrest France
|
|
|
|
INSP-Alarm Testing | 5/4/2011 | 5/6/2011 | 5/6/2011 | A | PART |
Forrest France
|
|
|
Issues noted today include DD trouble which supercedes supervisory condition for unit shutdown, non-latching ID smoke detectors, dampers at some basement ducts are not functional including L2S019 and L2S020, TS at the sprinkler riser are latching," AC power on" lamp at the panel remains illuminated during power off condition.
|
INSP-Final Inspection | 4/27/2011 | 4/28/2011 | 4/28/2011 | A | DEFR |
Forrest France
|
|
|
Request between 9a.m. & 10 a.m.----Earl Phone #: ###-####
|
FIR-Aging Inspection | 4/14/2011 | 4/14/2011 | 4/14/2011 | A | PEND |
Forrest France
|
|
|
Work in progress, per contractor one duct detector remains.
|
FIR-Aging Inspection | 3/16/2011 | 3/16/2011 | 3/18/2011 | | DONE |
Forrest France
|
|
|
In progress
|
FIR-Aging Inspection | 1/12/2011 | 1/12/2011 | 1/12/2011 | | DONE |
Forrest France
|
|
|
Site work in progress
|
INSP-Conference | 11/10/2010 | 11/12/2010 | 11/12/2010 | A | DONE |
Forrest France
|
|
|
On site conference with contractor regarding notification appliance locations at the climbing wall room and the rooftop playground area- plan modification to show revised locations. Also discussed protocol for new system transfer, demo work, new monitoring and impairments.
|
FIR-Aging Inspection | 9/3/2010 | 9/3/2010 | 9/3/2010 | | DONE |
Forrest France
|
|
|
Work in progress.
|
INSP-Final Inspection | 5/2/2011 | 5/3/2011 | | A | |
Forrest France
|
|
|
EARL Phone #: ###-####
|