Permit NumberFIR10-00137
StatusFinaled
Name FIRE SENTRY SYSTEMS
Site Address 1050 W STATE ST
Project NameYMCA-FIRE ALARM SYSTEM REPLACE
Customer Number 
ePlanReview 
Description
6-2-10: PLAN MODIFICATION
This plan modification is to provide additional in-duct detectors instead of open area detection, therefore all fire/smoke dampers will be shut down using in-duct detectors. This plan modification also includes incorporating previous redlines and review comments from the review dated 5/14/10.

5-14-10: This fire alarm permit is to replace the existing fire alarm panel and all components. This includes bringing the entire building up to meet current IFC and NFPA requirements. A manual system with full voice evacuation for notification, duct detectors for HVAC shutdown, elevator recall, and sprinkler system monitoring. There are also areas where smoke detectors are used in lieu of in-duct detectors to shut down fire/smoke dampers, but some of the dampers are shut down using in-duct detectors due to existing motor controls that are being left alone. There is no associated building permit.
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection8/30/20119/1/20119/1/2011APASS
DetailsForrest France
Noted correction items finished. Fire alarm permit finaled.
INSP-Final Inspection7/29/20117/29/20117/29/2011PPART
DetailsForrest France
Remainder of correction items include; repair one non-functional H/S at the womens locker room sauna, repair notification device at the first floor family restroom, adjust cd setting at one appliance in the basement level womens locker room. Need to verify EOL voltage and reverify notification functionality at the cardio area.
INSP-Conference7/27/20117/27/20117/27/2011ADONE
DetailsForrest France
Zach phone #: ###-#### Regarding corrections and final inspection schedule.
INSP-Final Inspection7/20/20117/21/20117/22/2011AFAIL
DetailsForrest France
Items noted during notification circut testing include sync issues at the basement level, various non-functional devices on the 1st floor, insufficient EOL voltage as measured, missing tone cycle preceeding and following the voice message, audibility at some areas such as the gym, spin, fitness, cardio and weight rooms do not appear sufficient.
INSP-Alarm Testing7/11/20117/11/20117/11/2011APART
DetailsForrest France
Ref. stamped plan set for annotations regarding devices tested to date.
INSP-Alarm Testing7/7/20117/7/20117/8/2011PPART
DetailsForrest France
Completed elevator device testing, SD at nac's and FACP, reviewed changes and adjustments to date, discussed items remaining including AC power light at the panel, guards at gym appliances, signage at doors to the FACP, as-builts/map, and notification testing schedule.
INSP-Alarm Testing6/27/20116/28/20116/28/2011APART
DetailsForrest France
MP stations tested satisfactory.
INSP-Alarm Testing6/27/20116/27/20116/28/2011APART
DetailsForrest France
Remainder of duct detectors tested okay.
INSP-Final Inspection6/20/20116/23/20116/24/2011PPART
DetailsForrest France
Completed testing of ID and DD at the first, second and third floors.
INSP-Conference6/6/20116/6/20116/6/2011PDONE
DetailsForrest France
Regarding inspection schedule.
INSP-Alarm Testing5/25/20115/26/20115/26/2011APART
DetailsForrest France
Completed testing of ID and DD devices at the basement levels. Noted tamper valve at the elevator machine room to be monitored, as-builts to reflect deleted and added devices, dampers have been repaired and verified for functionality. Previously noted correction items underway, some are finished. Ref. plan set for annotations.
INSP-Alarm Testing5/25/20115/25/20115/25/2011APART
DetailsForrest France
INSP-Alarm Testing5/4/20115/6/20115/6/2011APART
DetailsForrest France
Issues noted today include DD trouble which supercedes supervisory condition for unit shutdown, non-latching ID smoke detectors, dampers at some basement ducts are not functional including L2S019 and L2S020, TS at the sprinkler riser are latching," AC power on" lamp at the panel remains illuminated during power off condition.
INSP-Final Inspection4/27/20114/28/20114/28/2011ADEFR
DetailsForrest France
Request between 9a.m. & 10 a.m.----Earl Phone #: ###-####
FIR-Aging Inspection4/14/20114/14/20114/14/2011APEND
DetailsForrest France
Work in progress, per contractor one duct detector remains.
FIR-Aging Inspection3/16/20113/16/20113/18/2011 DONE
DetailsForrest France
In progress
FIR-Aging Inspection1/12/20111/12/20111/12/2011 DONE
DetailsForrest France
Site work in progress
INSP-Conference11/10/201011/12/201011/12/2010ADONE
DetailsForrest France
On site conference with contractor regarding notification appliance locations at the climbing wall room and the rooftop playground area- plan modification to show revised locations. Also discussed protocol for new system transfer, demo work, new monitoring and impairments.
FIR-Aging Inspection9/3/20109/3/20109/3/2010 DONE
DetailsForrest France
Work in progress.
INSP-Final Inspection5/2/20115/3/2011 A 
DetailsForrest France
EARL Phone #: ###-####