INSP-Final Inspection | 7/22/2010 | 7/23/2010 | 7/23/2010 | A | PASS |
Forrest France
|
|
|
Correction notice items are finished, final walkthrough passed. Fire sprinkler permit finaled.
|
INSP-Final Inspection | 7/22/2010 | 7/22/2010 | 7/22/2010 | P | FAIL |
Troy Cobbley
|
|
|
A different backflow preventor and water meter have been installed than what was submitted. The hydraulic calculations have been re-approved by tim. Several pendant heads are installed too close to surface mounted light fixtures. They need to be a minumum 3'-6" away. Several pendants also appear to be too close to ceiling fans. They need to be atleast 36" away or meet one of the exceptions. The riser service tag, head box, flow through correct orfice, removing/locking of handles were not verified.
|
INSP-Conference | 4/7/2010 | 4/7/2010 | 4/7/2010 | P | DONE |
Troy Cobbley
|
|
|
I spoke to Tim Frost and he and the code are ok with the area that was previously shown to be a sprinklered storage room now being a unsprinklered exterior patio.
|
INSP-Sprinkler Rough-in | 4/6/2010 | 4/7/2010 | 4/7/2010 | A | PASS |
Troy Cobbley
|
|
|
The overspaced sprinkler pendants have been corrected. Sprinkler piping is ok to cover.
|
INSP-Sprinkler Rough-in | 4/5/2010 | 4/6/2010 | 4/6/2010 | A | FAIL |
Troy Cobbley
|
|
|
Four pendant heads exceed the maximum calculated of 8' off of walls. Also the underground sprinkler piping is poly plastic not copper as per the drawings. Also the area marked "Storage" is now an exterior covered patio with the sprinkler protection deleted.
|