Permit Number | FIR10-00150 |
Status | Finaled |
Name |
ALLIED GENERAL FIRE & SECURITY
|
Site Address |
5369 W IRVING ST
|
Project Name | SIMPLOT BLG A SAHARA LAB REMOD |
Customer Number | |
ePlanReview | |
Description |
This quick permit is to provide a notification device due to a tenant remodel. The new device will be connected to the existing NAC panel 'C' circuit #2. Approval is subject to field measurement of the EOL voltage drop. For appliances with an operating voltage range of 16V - 33V, the minimum acceptable voltage is 19.6V with the AC power off. Any measurement below this voltage will be considered insufficient to run the NACs at the end of useful battery life of 20.4V. UL 864, Standard for Control Units for Fire Signaling Systems. There are no written review comments. Associated building permit: BLD09-01934 (J.R. SIMPLOT COMPANY - SAHARA LAB - REMODEL) This building is fire sprinklered for area increase and for fire flow. To expand the existing research laboratory into an adjacent 537 square foot area that was formerly used as a meeting room. Work is to include interior nonbearing walls, interior doors, mill work, a fume exhaust system, a cooling blower and connected condensing unit, interior finishes, and equipment. The work is required to comply with the approved drawings, with the plan review report, and with all applicable codes and ordinances. The fire sprinkler system is required to comply with NFPA 13 as regulated by the Fire Department. **CJW**.
|