Permit Number | FIR10-00189 |
Status | Finaled |
Name |
TAYLOR BROTHERS FIRE & SAFETY
|
Site Address |
390 E PARKCENTER BLVD Unit: 130
|
Project Name | Therapeutic Associates Inc |
Customer Number | |
ePlanReview | |
Description |
The Fire Sprinkler Scope of work consists of adding and relocating 5 sprinklers due to new wall and ceiling configuration. The existing system in this area, is a small 2½"'x2½" x1¼" grid. The area is located in the SW corner of the first floor. The main riser is in the NW corner. The existing water supply is reported as S-45, R-29, Q-3000. The existing hydraulic most remote area is located on the second floor of a two-floor building and the demand was reported as 319 GPM @ 40 PSI. This equates to a 4.8 cushion, which is approximately 10.7% below the available water supply. The area is a light hazard offices.
(THERAPEUTIC ASSOCIATES, INC - RIVERPOINT CENTER - STE 130) Permit is to remodel an existing 2,819 square foot office space for a new tenant. Approval contingent upon adhering to the approved plans on file. Work to include: demolition of interior non-bearing walls to create additional open office space, installation of new accessible customer service counter, installation of new interior non-bearing walls to create a charting area and an additional office, installation of stacked washer and dryer, and finishes in compliance with chapter 8 of the 2006 IBC. This building is fully fire sprinklered any alterations or modifications to the sprinkler system WILL REQUIRE A SEPARATE PERMIT and shall be installed per NFPA #13 as regulated by the fire department. **TLW**
|