Permit Information
Permit NumberFIR10-00196
StatusFinaled
Name SHILO AUTOMATIC SPRINKLER CO
Site Address 2734 E WINDSONG DR
Project NameBoulder Heights Residence.
Customer Number 
ePlanReview 
Description
The Fire Sprinkler Scope of work consists of a new residential sprinkler per modified NFPA 13D. In addition, to the NFPA 13D requirements one row of sidewall sprinklers separating the garage and the living space is to be provided, all corridors, closets and bathrooms are to be sprinklered. A dedicated 1½" poly pipe without a meter will supply the sprinkler system. The system will utilize CPVC piping. The pendent sprinklers are based upon a spacing of 18'x18'. The sidewall sprinklers are based on a spacing of 14'x14'.

? (reference Bld08-02280 and Bld09-01293)This permit is for the completion of an existing single family dwelling with original construction under Bld08-02280. The structure is a 3742 Sqft. one story single family dwelling with a basement (basement 1153 Sqft., first story 2648 Sqft.) with 448 Sqft of covered patio, 4 bedrooms, 3 1/2 baths and a 1067 Sqft. attached garage per the approved plans, plan review report, attached engineering and any notations. R-1A/DA zoning and setbacks per planning. CDM A modified 13D fire sprinkler system is required; see plan review notes for further details. SLR
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection8/9/20108/10/20108/10/2010APASS
DetailsTroy Cobbley
Permit finaled
INSP-Final Inspection8/6/20108/9/20108/9/2010PFAIL
DetailsTroy Cobbley
There is a pendant head located in a basement closet that has been installed under 4" from a wall. I contacted Tim about the garage door in the basement storage room that is obstructing a single pendant head. Tim stated that he was alright with it.
INSP-Sprinkler Rough-in5/13/20105/14/20105/14/2010PDONE
DetailsTroy Cobbley
Rough In Passed. The GC said he would put batt insulation over the piping first,over the visqueen and then the blow insulation.

Raul is the contact. Thanks Inspection requested from web by: Stan Beus Phone #: ###-####
INSP-Sprinkler Rough-in/Hydro5/12/20105/13/20105/13/2010PFAIL
DetailsTroy Cobbley
See the city approved plans for deficiencies that need corrected. This includes overspaced pendants and tenting/insulation issues.