Permit Information
Permit NumberFIR10-00202
StatusFinaled
Name TAYLOR BROTHERS FIRE & SAFETY INC
Site Address 398 N MITCHELL ST
Project NameCOTTONWOOD PLAZA-PANEL REPLACE
Customer Number 
ePlanReview 
Description
This fire alarm permit is to replace the existing fire alarm panel with new and use an internet/digital cellular communicator rather than a DACT. The existing addressable devices are being replaced with new, while existing conventional devices are to remain and be connected to the FACP using new addressable monitor modules. The only notification is one device used for the releasing system and is not part of building notification. There is no associated building permit.
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection5/12/20115/13/20115/13/2011APASS
DetailsTroy Cobbley
Permit finaled
INSP-Final Inspection5/12/20115/12/20115/12/2011PCANC
DetailsTroy Cobbley
cancelled due to time constraints rescheduled for tomorrow morning.
INSP-Final Inspection3/29/20113/30/20113/30/2011PFAIL
DetailsTroy Cobbley
Need to finish up inspection of duct smoke detectors. Need to connect the existing smoke detectors in the Liebert units to the facp and test. Need updated as-builts showing all devices and their locations. One remote annunciator for a duct smoke detector was activated without testing.
INSP-Alarm Testing3/25/20113/25/20113/25/2011PFAIL
DetailsForrest France
Noted mag lock at the north tenant server room did not drop out upon fire alarm activation- per plan this relay to be tied in. Also need verification the remainder of doors equiped with mag locks at the tenant spaces are in compliance as well.
INSP-Alarm Testing3/25/20113/25/20113/25/2011APART
DetailsForrest France
Damper operation at the electrical room verified okay, alarm condition reported- however a zone 6 flow was recieved at central station in additon to the zone 5 SD. Clean agent alarm condition tested but did not latch, tape and plastic cover at one SD in the server room removed while on site.
INSP-Final Inspection3/24/20113/24/20113/25/2011PNR
DetailsForrest France
robert Phone #: ###-####
INSP-Final Inspection3/3/20113/3/20113/3/2011PFAIL
DetailsTroy Cobbley
See the city approved plans for devices marled ok that have been tested. Items tested today were in the vacant space. Items needing corrected include repairing one fire/smoke damper in the electrical room and reprogramming the FACP panel to report alarm signals.We will need to re-verify these signals and test the devices in the two occupied spaces.
FIR-Aging Inspection3/3/20113/3/20113/3/2011 NR
DetailsTroy Cobbley
work is in progress
INSP-Final Inspection8/24/20108/27/20108/27/2010AFAIL
DetailsTroy Cobbley
The facp and dialer were verified. But inspection was stopped after it was found that instead of just monitor modules being installed at all of the existing duct smoke detectors, new duct smoke detectors had been installed which are being powered from the facp. Also duct smoke detectors are being used for the control of what appear to be fire/smoke dampers.