Permit Information
Permit NumberFIR10-00210
StatusFinaled
Name TREASURE VALLEY FIRE PROTECTION
Site Address 350 N MILWAUKEE AVE Unit: 2180
Project NameBTS - #2180 - CRAZY 8
Customer Number 
ePlanReview 
Description
The Fire Sprinkler Scope of work consists of relocating and adding sprinkler to a tenant improvement. The sprinklers are based on 120 Sqft spacing. The existing system is a 3"x3"x1ΒΌ" grid. Storage shall be limited to 12' per NFPA 13: 5.3.2. There shall be a minimum of the 18" clearance between the sprinkler deflector and the top of storage per NFPA: 13 8.5.6.1

(CRAZY 8 - BOISE TOWNE SQUARE - SPACE 2180) To remodel an existing 2,305 square feet retail tenant space for a new retail tenant. Work to include: [installation of interior non-bearing partition walls to create, a stockroom, a sales area, and an exiting hallway], installation of new flooring throughout, construction of a new storefront system, installation of suspended ceiling system per CISCA 0-2, new lighting, new ducts and diffusers, and interior finishes in compliance with ch. 8 of the 2006 IBC. This building is fully fire sprinklered any alterations to the sprinkler system shall be maintained per NFPA #13 as regulated by the fire department, The smoke evacuation system shall remain operational as originally installed under the 1985 UBC. The design, testing and utilization of industrial steel storage racks shall be in accordance with the RMI Specification for the Design, Testing and Utilization of Industrial Steel Storage Racks.**TLW**
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection6/3/20106/3/20106/3/2010PPASS
DetailsTroy Cobbley
Permit finaled
INSP-Sprinkler Rough-in5/20/20105/21/20105/21/2010APART
DetailsForrest France
Overhead rough-in at the drop and sheetrock lid ceilings is okay for cover. Discussed track lighting adjacent to sprinkler heads for possible obstruction and heat source issues with the contractor on site.