ePlanReview 
Description
This fire alarm permit is to remove an existing DACT that was originally serving as the sprinkler monitoring panel and install a new FACP. An AES panel is being provided for RF Communications. A manual pull station is being added to the system and the existing tamper and flow switches will be connected to the new FACP. There are no HVAC devices shown on the plans as part of this permit scope. If duct detectors exist or are required, a resubmittal shall be provided including these devices. There is no associated building permit.
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection10/15/201810/16/201810/16/2018PPASS
DetailsJim Page
Fire sprinkler tampers were not required for the size of the sprinkler system at time of install, PIV is locked in the open position and flow switch is monitored, final inspection for scope of work complete.

Ray McQueen, inspecting technician, building access limited to 1200 - 1500 10/16 Phone #: ###-#### Inspection requested via web by Rose Peterson
FIR-Aging Inspection9/26/20139/26/20139/26/2013 DEFR
DetailsForrest France
FIR-Aging Inspection2/28/20132/28/20132/28/2013 PEND
DetailsForrest France
Final pending PIV monitor
FIR-Aging Inspection11/29/201211/29/201211/29/2012 DEFR
DetailsForrest France
FIR-Aging Inspection8/30/20128/30/20128/31/2012 DEFR
DetailsForrest France
FIR-Aging Inspection5/31/20125/31/20126/1/2012 DONE
DetailsForrest France
FIR-Aging Inspection11/22/201111/22/201111/22/2011 PART
DetailsForrest France
Final pending tamper switch at the PIV.
FIR-Aging Inspection7/21/20117/21/20117/21/2011 PEND
DetailsForrest France
Ref. activity note 7/8
FIR-Aging Inspection3/17/20113/17/20113/18/2011 PEND
DetailsForrest France
FIR-Aging Inspection1/6/20111/6/20111/10/2011 DONE
DetailsForrest France
FIR-Aging Inspection11/3/201011/3/201011/3/2010APART
DetailsForrest France
See activity notes 5/20.
INSP-Final Inspection5/18/20105/20/20105/20/2010AFAIL
DetailsForrest France
Post indicator valve must be electronically supervised per IFC requirements. Approved plans also indicate a tamper switch at the PIV- final pending corrections. Remiander of work tested satisfactory, netcon rated 5 at the time of inspection.
INSP-Final Inspection9/10/20189/11/2018 A 
DetailsLee G Meredith
Building access is open, inspecting technician: Ray McQueen Phone #: ###-#### >> Inspection requested via web by Rose Peterson