INSP-Final Inspection | 10/15/2018 | 10/16/2018 | 10/16/2018 | P | PASS |
Jim Page
|
|
|
Fire sprinkler tampers were not required for the size of the sprinkler system at time of install, PIV is locked in the open position and flow switch is monitored, final inspection for scope of work complete.
Ray McQueen, inspecting technician, building access limited to 1200 - 1500 10/16 Phone #: ###-#### Inspection requested via web by Rose Peterson
|
FIR-Aging Inspection | 9/26/2013 | 9/26/2013 | 9/26/2013 | | DEFR |
Forrest France
|
|
|
|
FIR-Aging Inspection | 2/28/2013 | 2/28/2013 | 2/28/2013 | | PEND |
Forrest France
|
|
|
Final pending PIV monitor
|
FIR-Aging Inspection | 11/29/2012 | 11/29/2012 | 11/29/2012 | | DEFR |
Forrest France
|
|
|
|
FIR-Aging Inspection | 8/30/2012 | 8/30/2012 | 8/31/2012 | | DEFR |
Forrest France
|
|
|
|
FIR-Aging Inspection | 5/31/2012 | 5/31/2012 | 6/1/2012 | | DONE |
Forrest France
|
|
|
|
FIR-Aging Inspection | 11/22/2011 | 11/22/2011 | 11/22/2011 | | PART |
Forrest France
|
|
|
Final pending tamper switch at the PIV.
|
FIR-Aging Inspection | 7/21/2011 | 7/21/2011 | 7/21/2011 | | PEND |
Forrest France
|
|
|
Ref. activity note 7/8
|
FIR-Aging Inspection | 3/17/2011 | 3/17/2011 | 3/18/2011 | | PEND |
Forrest France
|
|
|
|
FIR-Aging Inspection | 1/6/2011 | 1/6/2011 | 1/10/2011 | | DONE |
Forrest France
|
|
|
|
FIR-Aging Inspection | 11/3/2010 | 11/3/2010 | 11/3/2010 | A | PART |
Forrest France
|
|
|
See activity notes 5/20.
|
INSP-Final Inspection | 5/18/2010 | 5/20/2010 | 5/20/2010 | A | FAIL |
Forrest France
|
|
|
Post indicator valve must be electronically supervised per IFC requirements. Approved plans also indicate a tamper switch at the PIV- final pending corrections. Remiander of work tested satisfactory, netcon rated 5 at the time of inspection.
|
INSP-Final Inspection | 9/10/2018 | 9/11/2018 | | A | |
Lee G Meredith
|
|
|
Building access is open, inspecting technician: Ray McQueen Phone #: ###-#### >> Inspection requested via web by Rose Peterson
|