Permit Information
Permit NumberFIR10-00231
StatusFinaled
Name ADT SECURITY SERVICES INC
Site Address 12302 W EXPLORER AVE
Project NameITT Educational Services Inc.
Customer Number 
ePlanReview 
Description
This fire alarm permit is to add/relocate/replace notification and initiating devices to accommodate a tenant improvement. A new remote power supply is being provided to replace an existing remote power supply, and a secondary fire alarm panel is being removed. The existing main Fire Alarm Control Unit is to remain.

Associated building permit: BLD10-00095 (ITT Educational Services INC.) Permit for tenant improvements to an existing 30,768 sq. ft. building with work to include the removal of some interior non-bearing partition walls, removal of two single user restrooms (not required per occupant load), installation of a folding partition (per attached engineering)to create additional open office area and a staff lounge. The wall between the existing student lounge areas will also be removed. The existing 1hour corridor is being downgraded as part of this permit. Per FIR05-00223 the building is equipped throughout with quick response sprinkler heads. This building is fully sprinklered for area increase: any alterations to the existing sprinkler system will require a separate permit and shall comply with NFPA13 as regulated by the City of Boise Fire Department. All work to be done per the approved plans, attached engineering, notations and any applicable codes. CDM
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection10/27/201010/29/201010/29/2010APASS
DetailsForrest France
Items on correction notice are finished. Fire alarm permit finaled. Inspection passed.
INSP-Final Inspection8/2/20108/2/20108/2/2010PFAIL
DetailsTroy Cobbley
Provide as-built drawings showing the additional fifteen existing duct smoke detectors, test all of the duct smoke detectors, provide verification of code compliant installation of the duct detectors (location & immediate shutdown), provide signage as per the review comment #30, provide map at the facp/annunciator as per review note #28, provide copy of the test signals from today.
INSP-Conference6/15/20106/15/20106/16/2010PDONE
DetailsTroy Cobbley
Art and I discussed the locations of the existing fire alarm devices. I told him unless they meet the requirements of a previous code the mounting heights will have to conform to current code.