Permit Information
Permit NumberFIR10-00246
StatusFinaled
Name ABSOLUTE FIRE PROTECTION
Site Address 10361 W EMERALD ST STE 100
Project NameEMERALD TECH BLDG 11
Customer Number 
ePlanReview 
Description
The Fire Sprinkler Scope of work consists of adding new walls and new ceiling in a portion of the building. The existing system is a tree system with 6" C-900 underground, 4" feed-main, 3" cross-main and 1½" branch lines. The original water supply was reported at S-60, R-20, Q-3000. The original calculations appear to have been calculated for .10/1599. The new sprinklers are being armed over from the existing outlets. Some sprinklers are being added by utilizing mechanical tees.

(PRECO ELECTRONICS)(BUILDING 11) First time build-out of a new tenant space to occupy a 6,111 sq. ft. portion in existing 11,900 sq. ft. existing SHELL (BLD06-01812) building per approved plans. Work to include construction of interior walls, doors, hardware, millwork, two accessible restrooms, drinking fountain, service sink, suspended ceiling, electrical, mechanical, sprinkler and alarm system modifications for the administrative offices of PRECO Electronics. Drs
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection7/15/20107/15/20107/15/2010PPASS
DetailsTroy Cobbley
permit finaled
INSP-Sprinkler Rough-in7/8/20107/9/20107/9/2010APASS
DetailsTroy Cobbley
The sprinkler piping is ok to cover.
INSP-Sprinkler Rough-in6/15/20106/15/20106/15/2010PPASS
DetailsTroy Cobbley
The sprinkler piping above the hardlids is ok to cover. Hangers and piping at other locations passed. Final sprinkler pendant spacing will be verified during another rough-in inspection.