INSP-Final Inspection | 8/19/2010 | 8/20/2010 | 8/20/2010 | A | PASS |
Troy Cobbley
|
|
|
Permit finaled
|
INSP-Sprinkler Rough-in/Hydro | 8/4/2010 | 8/4/2010 | 8/4/2010 | P | PASS |
Troy Cobbley
|
|
|
The overhead hydro test passed.
|
INSP-Sprinkler Rough-in | 8/2/2010 | 8/2/2010 | 8/2/2010 | P | PASS |
Troy Cobbley
|
|
|
Todays inspection verified sprinkler deflector distance from the deck, ESFR sprinkler SIN numbers and branchline hangers. Still need to complete the inspection on the riser, hydro tests...ect. Also needed are the main hangers "load splitters" addressed as per tim frost.
|
INSP-Sprinkler Rough-in/Hydro | 7/29/2010 | 7/30/2010 | 7/30/2010 | A | CANC |
Troy Cobbley
|
|
|
justin Phone #: ###-####//cancelled per Justin 7/30 @ 7:18am
|
INSP-Sprinkler Rough-in | 7/29/2010 | 7/29/2010 | 7/29/2010 | P | PART |
Troy Cobbley
|
|
|
The offices 100, 102, 103 and 104 are actually being used for storage of paintings. These areas will need to be addressed as Ordinary Hazard. Also per the fitter the ceilings in these same areas are not going to be installed. Resubmittals will be required. That being said the sprinkler piping can be covered. All of the overhead sprinkler piping was inspected today and passed except a lift will not be available until next week to verify heads, distances from the deck and hangers. There are still hanger issues being addressed by the plan reviewer and Treasure Valley Fire. So hangers and sway bracing has not been inspected yet. Insulation neeeds to be installed at the deck as discussed above the upper mezzanine offices and the insulation that is hanging down in the warehouse needs to be repaired.
|
INSP-Supply line flush | 7/9/2010 | 7/9/2010 | 7/9/2010 | P | PART |
Forrest France
|
|
|
UG fire supply line flush completed satisfactory.
|
INSP-Sprinkler Rough-in/Hydro | 7/8/2010 | 7/9/2010 | 7/9/2010 | A | PART |
Forrest France
|
|
|
Underground fire supply line hydrostatic test passed.
|
INSP-Sprinkler Rough-in | 7/7/2010 | 7/7/2010 | 7/7/2010 | P | PASS |
Troy Cobbley
|
|
|
The underground stub-in is ok for cover.
|