Permit Information
Permit NumberFIR10-00302
StatusFinaled
Name TREASURE VALLEY FIRE PROTECTION
Site Address 865 W AMITY RD
Project NameAmity Warehouse Upgrade
Customer Number 
ePlanReview 
Description
The Fire Sprinkler Scope of work consists of changing a double tree system into a compound grid system. There are no new sprinklers being added under this permit. The existing risers will have new backflow preventers installed. The system will protect shoes in cardboard boxes 16' high on wood pallets with 8' aisles. The building ceiling height is 22'-6". According to the contractor, the systems were apparently installed in 1975. The original system design was .30/3058.

There is no associated building permit.
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection8/26/20108/31/20108/31/2010APASS
DetailsForrest France
Fire sprinkler permit finaled.
INSP-Final Inspection8/26/20108/31/20108/31/2010APASS
DetailsForrest France
Noted corrections field verified, fire alarm interconnects tested okay.
INSP-Final Inspection8/25/20108/26/20108/26/2010ADEFR
DetailsForrest France
Rescheduled 8/31
INSP-Final Inspection8/11/20108/11/20108/11/2010PFAIL
DetailsTroy Cobbley
The earthquaking has been addressed and both of the risers easily passed the required forward flush. Per Lonnie the storage is being reduced to no higher than the designed 16' but was not complete yet. The fire alarm permit still needs to be addressed.
INSP-Sprinkler Rough-in8/9/20108/9/20108/9/2010PFAIL
DetailsTroy Cobbley
Sizing, placement and hangers for the new sprinkler piping was inspected and passed. The locations of the earthquake bracing does not match plans and in some locations the two way and four way braces are in switched locations. Also the maximum storage height is listed as 16'-0" but the storage is up to 19'-6" in several locations. Also no fire alarm permit has been applied/issued for the tamper switches and flow switches. This fire sprinkler permit will not be finaled until an alarm permit has been applied for. A forward flush test was not performed due to the design possibly being changed due to the new storage height. An above ground hydro test will not be required.