Permit Information
Permit NumberFIR10-00303
StatusFinaled
Name ALARMCO
Site Address 10335 W EMERALD ST
Project NameEMERALD TECH BLDG 10
Customer Number 
ePlanReview 
Description
This fire alarm permit is to connect three duct detectors to the existing system and indicate the new location of the existing fire alarm control panel. Notification is not part of this permit scope of work. There is an existing AES RF wireless monitoring unit with an IntelliTap module installed under FIR10-00279.

Associated building permit: BLD10-000779 (PRECO ELECTRONICS (BUILDING 10) First time build-out and finish of 12,321 sq. ft. SHELL building (BLD06-01811) for use as Manufacturing Facility with Production/Radar Range, Packaging, R& D Radar Range, Support Administration, Lunch Room, Conference Room, Lobby & Accessible Restrooms, per approved plans. Work to include construction of interior non-bearing walls to create noted rooms and areas; suspended ceiling grid in specified areas, interior millwork, interior finishes and electrical, mechanical, plumbing, sprinkler and alarm systems per code. drs
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection7/8/20107/9/20107/9/2010APASS
DetailsTroy Cobbley
Permit finaled
INSP-Final Inspection7/7/20107/8/20107/8/2010AFAIL
DetailsTroy Cobbley
All devices were tested but the duct detectors have been wired to a single zone instead of the three individual zones per the approved plans. I waited on site while the alarm installer tried to get things changed but when we tested the duct on zone 6 the hvac unit did not shut down. The inspection was stopped. All duct smoke detectors will need to be retested to verify shutdown and correct zone labeling/monitoring and a signal report will need to be provided. A map at the FACP is required as well.