Permit Information
Permit NumberFIR10-00307
StatusFinaled
Name ALARMCO
Site Address 10361 W EMERALD ST Unit: 100
Project NameEMERALD TECH BLD # 11 T.I.
Customer Number 
ePlanReview 
Description
This fire alarm permit is to add two duct detectors to the existing fire alarm system, provide connections for monitoring functions for an FM-200 system, and re-circuit an existing tamper switch to accommodate a tenant improvement. There is an existing AES panel with an IntelliTap module installed under FIR10-00280.

Associated building permit: BLD10-00780 (PRECO ELECTRONICS) (BUILDING 11) First time build-out of a new tenant space to occupy a 6,111 sq. ft. portion in existing 11,900 sq. ft. existing SHELL (BLD06-01812) building per approved plans. Work to include construction of interior walls, doors, hardware, millwork, two accessible restrooms, drinking fountain, service sink, suspended ceiling, electrical, mechanical, sprinkler and alarm system modifications for the administrative offices of PRECO Electronics. drs.
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection8/4/20108/5/20108/5/2010APASS
DetailsTroy Cobbley
Permit finaled.
INSP-Final Inspection8/4/20108/4/20108/4/2010PFAIL
DetailsTroy Cobbley
The trouble signal from the fm200 panel was received at the facp as a supervisory. After that was changed we found that the signals were not being received correctly at the monitoring station. I stayed as long as possible but corrections could not be completed. Will need to be rescheduled.
INSP-Final Inspection7/30/20107/30/20107/30/2010PFAIL
DetailsTroy Cobbley
Bill was not available to do the inspection. No one was on site either. No inspection was performed.
INSP-Final Inspection7/19/20107/20/20107/20/2010APART
DetailsTroy Cobbley
A temporary occupancy was given until the interconnections with the FM200 system has been tested.
INSP-Sprinkler Rough-in/Hydro7/16/20107/19/20107/19/2010AFAIL
DetailsTroy Cobbley
The duct smoke detectors and tamper switches tested ok but the facp went into trouble. I left and later returned to the project to see if the issue had been resolved and found that the technicians were still trouble shooting.
INSP-Final Inspection7/16/20107/16/20107/16/2010PCANC
DetailsTroy Cobbley
There are still issues with hvac shutdown. No inspection performed. To be rescheduled for monday morning.
INSP-Final Inspection7/15/20107/16/20107/16/2010ACANC
DetailsTroy Cobbley
Please call Bill at ###-#### with inspection time Phone #: ###-#### >> Inspection requested via web by Lori Brungardt Inspection cancelled from web by: Lori Brungardt