Permit NumberFIR10-00336
StatusFinaled
Name MOUNTAIN ALARM
Site Address 7940 W RIFLEMAN ST Unit: 140
Project NameFidelity Investments
Customer Number 
ePlanReview 
Description
9/7/10 2nd PLAN MODIFICATION - 1 (one) initiating device is affected by this modification.
This plan modification is to split the notification circuit into two separate circuits to ensure voltage drops are not exceeded.

8/27/10 PLAN MODIFICATION
This plan modification is to replace the originally submitted horn/strobes with Wheelock devices and the addition of a second waterflow monitoring zone. In addition, zones have been changed for the duct detectors (all are now on Zone #6 rather than split into two zones as previously submitted), and a candela has been increased and a synchronization module has been provided. The flow switches are in the riser room shown on the key plan.

8/5/10
This fire alarm permit is to provide notification devices, manual pull stations, non-required (customer requested) smoke detection, and HVAC monitoring due to a tenant remodel.

Associated building permit: BLD10-01246 (Fidelity Investments) Permit for tenant improvements to an existing 4,150 sq. ft. tenant space with work to include two new accessible restrooms, construction of new interior non-bearing partition walls, Suspended ceiling, new vestibule, HVAC ducting, fire sprinkler, electrical and all related interior finishes. All work to be done per the approved plans, plan review report and any notations. This is a fully sprinklered building; any alterations to the existing sprinkler system will require a separate permit and shall comply with NFPA 13 as regulated by the City of Boise fire department. CDM
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection9/9/20109/9/20109/9/2010PPASS
DetailsTroy Cobbley
Permit finaled
INSP-Final Inspection8/27/20108/30/20108/30/2010AFAIL
DetailsTroy Cobbley
Provide one additional smoke detector in the ceiling pocket outside of the conference room. Also the EOL did not meet the minimum 19.6 volts. It appears that the notification circuit wil need to be split. This modification will require a resubmittal. Also the horns did not sync.
INSP-Final Inspection8/25/20108/26/20108/26/2010AFAIL
DetailsTroy Cobbley
The audio/visual devices are mounted too low. Need to test the a/v's and the smoke detectors. The tamper switch and flow switch were verified.
INSP-Final Inspection8/25/20108/25/20108/25/2010PCANC
DetailsTroy Cobbley
Per Chris Farnsworth the hvac units were not shutting down upon activation of the duct smoke detectors. Inspection to be rescheduled for tomorrow morning.