Permit Information
Permit NumberFIR10-00341
StatusFinaled
Name ABSOLUTE FIRE PROTECTION
Site Address 1746 W STATE ST
Project NameANYTIME FITNESS
Customer Number 
ePlanReview 
Description
The Fire Sprinkler Scope of work consists of changing a space from ordinary hazard to light hazard. The existing system has a 4" feed and cross mains with 2" branch lines. All sprinklers within the space will be changed to quick response type.

This building is fire sprinklered for building area increase and for fire area. To expand an existing 3,504 square feet tenant space by about 708 square feet into an adjacent area. After the expansion, this tenant space will have a total floor area of about 4,212 square feet and will be used as an exercise gym. Work is to include two toilet/shower rooms accessible to the disabled, interior nonbearing walls, gypsum board ceiling over the toilet/shower rooms, new ceiling tiles in the existing suspended ceiling grid, panic door hardware, wall furring over an existing metal exterior door, and interior finishes. The work is required to comply with the approved drawings, with the plan review report, and with all applicable codes and ordinances. The fire sprinkler system is required to comply with NFPA 13 as regulated by the Fire Department. If there is combustible material exposed within the concealed space above the suspended ceiling, the area above the suspended ceiling is required to be fire sprinklered. **CJW**
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection8/24/20108/24/20108/24/2010APASS
DetailsForrest France
Fire sprinkler permit finaled.
INSP-Sprinkler Rough-in8/17/20108/17/20108/17/2010PPART
DetailsForrest France
Overhead fire sprinkler work per the scope of remodel is approved for cover at the drop ceilings.
INSP-Sprinkler Rough-in8/13/20108/16/20108/16/2010AFAIL
DetailsForrest France
Noted one upright head yet to be replaced with quick response, upright coverage at either side of a beam appears overspaced.