INSP-Final Inspection | 3/17/2011 | 3/18/2011 | 3/18/2011 | A | PASS |
Forrest France
|
|
|
C/N items completed. Inspection passed. Fire sprinkler permit finaled.
|
INSP-Final Inspection | 3/15/2011 | 3/17/2011 | 3/17/2011 | A | PART |
Forrest France
|
|
|
Verified dry system pressure switch and outside bell operations. Need to complete forward flow test per last inspection notes dated 2/14 and per plan review revision notes item #1 dated 8/11/10. Missing automatic air maintenance device per NFPA 13 7.2.6.5.1 or meet sec. 7.2.6.5.2.
|
INSP-Final Inspection | 3/14/2011 | 3/15/2011 | 3/15/2011 | A | DEFR |
Forrest France
|
|
|
We will be there for the 7:30am final. Ken is the contact. Thanks Phone #: ###-#### >> Inspection requested via web by Stan Beus
|
INSP-Final Inspection | 2/9/2011 | 2/14/2011 | 2/14/2011 | A | PART |
Forrest France
|
|
|
Final pending program change for the dry system pressure switch at the FACP and outside bell connection. Walkthrough passed, trip testing completed okay. Need to forward flow the DCVA.
|
INSP-Final Inspection | 2/2/2011 | 2/3/2011 | 2/3/2011 | A | CANC |
Forrest France
|
|
|
Mike B is the contact. Thanks Phone #: ###-#### >> Inspection requested via web by Stan Beus Inspection cancelled from web by: Stan Beus
|
INSP-Final Inspection | 2/2/2011 | 2/4/2011 | 2/2/2011 | A | CANC |
Forrest France
|
|
|
Mike B is the contact. We understand this is scheduled for 7:30 am. Thanks Phone #: ###-#### >> Inspection requested via web by Stan Beus Inspection cancelled from web by: Stan Beus
|
INSP-Final Inspection | 2/2/2011 | 2/3/2011 | 2/2/2011 | A | CANC |
Forrest France
|
|
|
Mike B is the contact. We understand this is
scheduled for 7:30am Phone #: ###-#### >> Inspection requested via web by Stan Beus Inspection cancelled from web by: Stan Beus
|
INSP-Sprinkler Rough-in/Hydro | 1/31/2011 | 2/1/2011 | 2/1/2011 | P | PART |
Forrest France
|
|
|
Concluded satisfactory 24 hr. pneumatic test of the dry system within allowable leakage per NFPA 13.
|
INSP-Sprinkler Rough-in | 1/28/2011 | 1/31/2011 | 1/31/2011 | P | PART |
Forrest France
|
|
|
Begin 24 hr. air test of the new dry system 12:30 PM @45psig.
|
INSP-Final Inspection | 1/26/2011 | 1/28/2011 | 1/28/2011 | A | NR |
Forrest France
|
|
|
Need to complete 24 hr. air test of the new dry system per NFPA 13 2007 24.2.2.1
|
INSP-Conference | 1/6/2011 | 1/6/2011 | 1/11/2011 | P | DONE |
Forrest France
|
|
|
|
INSP-Sprinkler Rough-in/Hydro | 1/6/2011 | 1/7/2011 | 1/10/2011 | A | PART |
Forrest France
|
|
|
Overhead hydrostatic test for the new first floor system only, passed.
|
INSP-Sprinkler Rough-in | 12/16/2010 | 12/17/2010 | 12/17/2010 | P | PART |
Forrest France
|
|
|
Correction items at the first floor per last inspection completed- okay to cover with the exception of the kitchen area grid ceilings incomplete at this time.
|
INSP-Sprinkler Rough-in | 12/6/2010 | 12/6/2010 | 12/6/2010 | P | FAIL |
Forrest France
|
|
|
Rough-in inspection for the 1st floor completed- Noted exposed combustible construction lacking coverage at the open area south end, need to maintain 130 ft2 max spacing at the kitchen, field modifications in branchline routing at the east entry vestibule need to be installed per plan or proved by new calcs as five heads are now fed from a single 1" outlet. See redline areas on plan set for locations. Note: okay to cover remainder of installation.
|
INSP-Sprinkler Rough-in/Hydro | 11/4/2010 | 11/4/2010 | 11/4/2010 | A | PART |
Forrest France
|
|
|
Dry system hydro passed.
|
INSP-Sprinkler Rough-in/Hydro | 11/2/2010 | 11/3/2010 | 11/3/2010 | P | PART |
Forrest France
|
|
|
Overhead hydrostatic test of the new dry system passed.
|
INSP-Sprinkler Rough-in | 10/19/2010 | 10/21/2010 | 10/22/2010 | A | PART |
Forrest France
|
|
|
Corrections at the second floor okayed for cover.
|
INSP-Sprinkler Rough-in | 10/18/2010 | 10/18/2010 | 10/18/2010 | P | FAIL |
Forrest France
|
|
|
See inspection notes on stamped plan dated 9/17- provide coverage at two pockets, min. spacing at two pendent heads in the corrdior is exceeded.
|
INSP-Sprinkler Rough-in | 10/18/2010 | 10/18/2010 | 10/18/2010 | A | PART |
Forrest France
|
|
|
Okay to cover basement level overhead fire sprinkler install.
|
INSP-Sprinkler Rough-in | 10/15/2010 | 10/15/2010 | 10/15/2010 | P | PART |
Forrest France
|
|
|
Re-inspection for relocated head in the basement okayed.
|
INSP-Sprinkler Rough-in | 10/7/2010 | 10/8/2010 | 10/8/2010 | A | PART |
Forrest France
|
|
|
See plans for locations red-lined with today's inspection notes.
|
INSP-Sprinkler Rough-in | 10/7/2010 | 10/8/2010 | 10/7/2010 | A | CANC |
Forrest France
|
|
|
Nate is the contact. Thanks Phone #: ###-#### >> Inspection requested via web by Stan Beus Inspection cancelled from web by: Stan Beus
|
INSP-Sprinkler Rough-in/Hydro | 9/16/2010 | 9/17/2010 | 9/17/2010 | A | PART |
Troy Cobbley
|
|
|
The rough-in for the basement was stopped after it was found that the 3" sch. 10 main as shown on the city approved plans was not installed. The 2nd floor dry and wet system rough-in inspection passed except as noted in red on the city approved plans and the piping can be covered. The overhead hydro on dry system failed due to a drop from 212 psi to 208 psi after two hours.
|
INSP-Sprinkler Rough-in/Hydro | 9/9/2010 | 9/10/2010 | 9/10/2010 | P | PART |
Forrest France
|
|
|
Overhead hydrostatic test of the wet system riser adjacent to the dry valve passed.
|
INSP-Sprinkler Rough-in | 8/13/2010 | 8/16/2010 | 8/16/2010 | A | PART |
Forrest France
|
|
|
Overhead work at two restrooms basement level as initialed and annotated with today's date are okay for ceiling cover.
|