ePlanReview 
Description
The Fire Sprinkler Scope of work consists of a tenant improvement to change an existing space into a yoga studio. The designer indicated the studio portion of the space would be maintained at an ambient temperature exceeding 120ยบ F; therefore, intermediate temperature sprinklers will be utilized.

________________________________________

Building Department Scope:

Permit is to remodel an existing 3,892 square foot office space to be a yoga studio. Approval is contingent upon adhering to the approved plans on file. Work to include: construction of interior non-bearing walls to create a fully accessible changing rooms and a large workout (yoga) room, installation of new accessible showers, installation of new hi/low drinking fountain, installation of new doors and hardware, and finishes in compliance with chapter 8 of the 2006 IBC. This building is fully fire sprinklered any alterations or modifications to the sprinkler system WILL REQUIRE A SEPARATE PERMIT and shall be installed per NFPA #13 as regulated by the fire department. **TLW**--TRF--
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection8/24/20108/25/20108/25/2010APASS
DetailsForrest France
Fire sprinkler permit passed final walkthrough, one remaining tile at a pendent head installed while on site. Permit finaled.
INSP-Sprinkler Rough-in/Hydro8/18/20108/18/20108/18/2010APART
DetailsForrest France
Correction items noted at the previous inspection verified for completion- Overhead okayed for cover.
INSP-Final Inspection8/13/20108/17/20108/17/2010APART
DetailsForrest France
Overhead sprinkler system modifications okayed with the exception of three missing retainer straps at new top beam clamps for armover hangers and one overspaced pendent head to an adjacent wall. See stamped plan set for locations. Remainder of work approved for cover. Need to verify existing system is current with an annual inspection.