Permit Information
Permit NumberFIR10-00398
StatusFinaled
Name QUALITY ELECTRIC INC
Site Address 3176 S DENVER WAY
Project NameST LUKE'S REFERENCE LABORATORY
Customer Number 
ePlanReviewNo
Description
1/14/11: PLAN MODIFICATION (10 initiating devices affected): This plan modification is to show field modifications to some notification device placement, provide in-duct detectors to f/s dampers not originally known to be a part of the project, and to eliminate some of the duct detectors not needed due to common returns.
8/20/10:
This fire alarm permit is to provide notification and initiating devices to accommodate a tenant improvement. Devices include all new horn/strobes (any existing notification devices are to be removed), pull stations, HVAC monitoring, and in-duct detectors for new F/S dampers. The notification devices are to be connected to new remote power supplies. The initiating devices are to be connected to the existing fire alarm signal line circuit. This building does not require the full manual system (only sprinkler monitoring, elevator recall, and HVAC), however it was requested by the customer.
NOTE TO INSPECTOR: The fire sprinkler permit (FIR10-00125) is attached to the demo building permit (BLD09-02080).
Associated building permit: BLD10-00044 (ST. LUKE'S - REFERENCE LABORATORY) To remodel an existing two story 31,625 sq. ft. building into a medical laboratory per approved plans. Demolition work is under separate permit, BLD09-02080. Work to include construction of interior walls in conjunction with remaining existing walls to create office, work, laboratory and support areas; conference / training room on second floor with existing offices; upgrade restrooms, showers, drinking fountains, doors, door hardware and clear floor spaces & latch side clearance at all doors; work on electrical, mechanical, plumbing, sprinkler, alarm and security systems to comply with current adopted codes and ordinances. Separate applications and permits required for sprinkler & alarm system modifications as regulated by the fire department, before being worked on. NOTE: This building is fully fire sprinklered with all heads being changed to quick response to allow non-rated corridors. Drs
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection1/21/20111/21/20111/21/2011PPASS
DetailsForrest France
Inspection notes 1/21/11- Flow switch repaired and retested okay. Audible notification adjustments okayed. Fire alarm permit final approved.
INSP-Final Inspection1/20/20111/20/20111/21/2011PPART
DetailsForrest France
Inspection notes 1/20/11- Completed acceptance testing including initiating and notification devices, sprinkler monitoring, and elevator control functions. Verified offsite monitoring. Flashing hat at the elevator is not required due to original installation date of the equipment per plan review. Flow switch at the wet system riser did not pass operational testing. Remainder of items tested okay.
INSP-Final Inspection1/18/20111/19/20111/21/2011APART
DetailsForrest France
Inspection notes 1/19/11- Completed project walkthrough- noted some locations where audibility may be insufficient, cd rating at the second floor breakroom adjusted, one DD is supply side located, "shadowed" areas to be verified during functional testing. Verified as-builts per request.
INSP-Conference12/21/201012/22/201012/22/2010ADONE
DetailsForrest France
Regarding field modifications and plan resubmital.
FIR-Aging Inspection11/12/201011/12/201011/12/2010 DONE
DetailsForrest France
Site work in progress, construction underway.
INSP-Conference8/31/20108/31/20109/1/2010PDONE
DetailsForrest France
Regarding notification appliance locations with respect to equipment layout at one area.