Permit Information
Permit NumberFIR10-00402
StatusFinaled
Name ALLIED GENERAL FIRE & SECURITY
Site Address 8233 W FRANKLIN RD
Project NameCAFE RIO-FRANKLIN TOWNE PLAZA
Customer Number 
ePlanReviewNo
Description
This fire alarm permit is to provide a non-required (owner requested) automatic fire alarm system in a partially sprinklered tenant space. The system full area smoke detection, full notification, HVAC shutdown, and heat detectors.

Associated building permit: BLD10-01207 (CAFE RIO - EAST END OF BUILDING) (8-16-10 PLAN MODIFICATION TO CHANGE THE CURP RAMP AND TO CHANGE THE MOUNTING OF THE TRACK FOR THE ROLL-DOWN FIRE DOOR). Partial fire sprinkler system required for fire area occupant load. To remodel an existing 2,580 square foot tenant space and convert it to a restaurant with a kitchen. Work it to include 2 restrooms accessible to the disabled, interior nonbearing walls, four (4) Type I grease hoods, one (1) Type II hood, interior decorative canopies, a suspended decorative log ceiling element, suspended acoustical ceilings, structural work to support new roof top equipment (concrete footings, steel and wood columns, steel and wood beams, etc.), kitchen equipment, a grease trap, and finishes. Transfer blocks and bottom cord sleepers will be added to the existing roof trusses as part of the structural modifications needed to support hoods and new roof top equipment. In addition, a 2-hr fire-resistance-rated fire barrier wall will be constructed to completely separate this building, the canopy included, into two separate fire areas. The work is required to comply with the approved drawings, with the plan review report, and with all applicable codes and ordinances. The fire area containing this tenant space is required to be fire sprinklered in conjunction with this permit. The fire sprinkler system is required to comply with NFPA 13 as regulated by the Fire Department. Interior nonstructural demolition was done under permit BLD10-01546. **CJW**
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection9/9/20109/10/20109/10/2010APASS
DetailsForrest France
Noted corrections verified for compliance. Fire alarm testing passed, permit finaled.
INSP-Final Inspection9/8/20109/9/20109/9/2010AFAIL
DetailsTroy Cobbley
Still need to test the duct smoke detectors, heat detectors and smoke detectors. A single smoke detector needs to be provided on the south side of the beam and the two smoke detectors in the center of the dining area need to be mounted at the roof deck instead of the bottom chord of the trusses. One strobe needed to have the candella increased due to overspacing. The PIV tamper switch was wired backwards and one other tamper switch had been by-passed. Both were repaired while I waited. The EOL tested ok as well as the sprinkler system devices and the hood suppression system. Signal reports are needed showing todays work.