Permit NumberFIR10-00409
StatusFinaled
Name DEBEST FIRE PROTECTION
Site Address 10221 W EMERALD ST
Project NamePiramal Critical Care
Customer NumberSEE COMMENTS
ePlanReviewNo
Description
The Fire Sprinkler Scope of work consists of adding, relocating and removing sprinklers to accommodate a new tenant. Approximately, 27 sprinklers are being changed from pendent to upright sprinklers. A new partial branch line will be connected to the existing 3" main and then connected to the existing 1ΒΌ" branch lines in this grid type piping system. The design is based on boxed or pallet storage not to exceed 5' in height per Bob Hosac of RS Hosac

Building Department Scope:

Permit for a tenant improvement to an existing 19,035 sq. ft. building to combine all existing tenant spaces into one tenant space with work to include the removal of interior non-bearing partition walls, removal of one restroom and the extension of some of the interior partition walls up to the roof deck. The existing lighting fixtures will be reused. All work to be done per the approved plans, plan review report and any notations. This is a fully sprinklered building; any alterations to the sprinkler system will require a separate permit and shall comply with NFPA13 as regulated by the Boise City Fire Department. No Racking is allowed under this permit. A separate racking permit is required for any racking over 8 feet in height. CDM
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection9/1/20109/1/20109/1/2010PPASS
DetailsTroy Cobbley
Permit finaled
INSP-Final Inspection8/30/20108/31/20108/31/2010PFAIL
DetailsTroy Cobbley
Two heads as discussed need to have separate supplies from the branchline since the area does not appear to qualify for "Room Design" method of hydraulic calculations. I also noted that one pendant head in the office area is located too close to a wall and will need to be relocated as well as missing canopies provided. The fire sprinkler system has not been inspected for 10 years.