Permit Information
Permit NumberFIR10-00415
StatusFinaled
Name DOHERTY ELECTRIC
Site Address 950 W STATE ST
Project NameFirst Presbyterian Church TI
Customer Number 
ePlanReviewNo
Description
1-26-11 PLAN MODIFICATION (no initiating devices affected): This plan modification is to incorporate field changes and implemented redlines and review comments from previous reviews.

10-5-10:This fire alarm permit is to provide speaker strobes throughout the new tenant improvement area, a new duct detector, and relocation/re-mounting of existing pull stations to meet current ADA requirements.
Associated building permit: BLD10-00842 (FIRST PRESBYTERIAN CHURCH - LINDSAY HALL REMODEL) Fire sprinklers used for building area increase. To remodel the basement (3,528 square feet), first story (3,528 square feet), and second story (3,528 square feet) of the existing Lindsay Hall portion (East end of building) of the First Presbyterian Church. Work is to include upgrading the restrooms on all 3 stories to be accessible to the disabled, upgrading the enclosure of the East stairway to be 1-hr fire-resistance-rated, constructing interior walls, installing new folding partitions, and creating new openings in an existing masonry wall (steel headers and trimmers). Work also includes exterior windows, doors, suspended acoustical ceilings, interior finishes, and millwork. The work is required to comply with the approved drawings, with the plan review report, and with all applicable codes and ordinances. Lindsay Hall will be fully fire sprinklered throughout in conjunction with this permit. The fire sprinkler system of the entire First Presbyterian Church building is required to comply with NFPA 13 as regulated by the Fire Department. **CJW**
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection3/22/20113/24/20113/24/2011APASS
DetailsForrest France
Corrections finished. Fire alarm passed final inspection.
INSP-Final Inspection3/15/20113/17/20113/17/2011AFAIL
DetailsForrest France
Speakers are not operational.
INSP-Final Inspection3/14/20113/15/20113/15/2011ACANC
DetailsForrest France
7:30am if possible. Nick is the contact his no. is ###-####. Phone #: ###-#### >> Inspection requested via web by Shawna Gates Inspection cancelled from web by: Shawna Gates
INSP-Final Inspection2/9/20112/14/20112/14/2011AFAIL
DetailsForrest France
C/N items include; pressure switch at the dry system must report as an alarm condition and initiate activation of the outside bell, adjust cd settings at the first floor vestibule and adjacent to the reception desk per plan, provide notification at the employee work room per plan review red line notes, mechanical room duct detector activates general alarm condition, provide a WP notification appliance at the 2nd floor shower room, replace 15cd strobe only per plan at the 2nd floor west corridor. KH monitor tested okay, remainder of fire sprinkler riser points also okayed.
INSP-Sprinkler Rough-in/Hydro2/9/20112/14/20112/9/2011ACANC
DetailsForrest France
Please schedule for 7:30am. Rafe with Protex is the contact his cell no. is ###-####. Thank you.
Phone #: ###-#### >> Inspection requested via web by Shawna Gates Inspection cancelled from web by: Shawna Gates
INSP-Final Inspection1/27/20112/1/20111/31/2011ANR
DetailsForrest France
INSP-Final Inspection1/27/20111/28/20111/27/2011ACANC
DetailsForrest France
Request for 7:30am inspection. Rafe with Protex is the contat, his cell no. is ###-####. Phone #: ###-#### >> Inspection requested via web by Shawna Gates Inspection cancelled from web by: Shawna Gates
INSP-Alarm Testing11/15/201011/15/201011/16/2010PPART
DetailsForrest France
Notification testing at the basement level previously completed- ref. building permit activity notes.