INSP-Final Inspection | 9/24/2010 | 9/24/2010 | 9/24/2010 | P | PASS |
Forrest France
|
|
|
Fire alarm permit work okayed for final, address switch repaired while on site. Inspection passed.
|
INSP-Alarm Testing | 9/24/2010 | 9/24/2010 | 9/24/2010 | P | PASS |
Forrest France
|
|
|
Reinspection for noted correction items passed at the 2nd, 5th and 6th floors.
|
INSP-Final Inspection | 9/23/2010 | 9/23/2010 | 9/24/2010 | P | FAIL |
Forrest France
|
|
|
Correction items include relocate three SD too close to HVAC diffusers, adjust cd setting per plan at one room 5th floor, voice evacuation message does not meet intelligibility or audibility requirements.
|
INSP-Alarm Testing | 9/22/2010 | 9/22/2010 | 9/22/2010 | A | PART |
Forrest France
|
|
|
After hours inspection scheduled 9/23 PM.
|