Permit Information
Permit NumberFIR10-00423
StatusFinaled
Name SIMPLEX GRINNELL
Site Address 1221 W IDAHO ST
Project NameIdaho Power Company
Customer Number 
ePlanReviewNo
Description
This fire alarm permit is to extend the existing voice evacuation system and add smoke detectors to accommodate a tenant remodel. A new NAC remote power supply/panel is being provided to accommodate the visual portion of the new notification devices. The speakers will be added to existing speaker circuits.

Associated building permit: BLD10-01305 (IDAHO POWER COMPANY) Permit for minor interior improvements to the to the second, third, fifth and sixth floors. The work on the third, fifth and sixth is work that has already been completed and is minor in nature consisting of the construction of Steelcase Pathways demountable wall system to create small office and conference room areas with no change in occupant load. The wall system is to be installed per ESR 1829 attached to the plans. Work on the second floor is similar in nature with K-Wall systems approved under previous permits with work to include retrofit of lighting with more efficient products minor HVAC work and related interior finishes with no change in occupant load. The existing corridor is to remain in tact. All work to be done per the approved plans. This is a fully sprinklered building any alterations to the sprinkler system will require a separate permit and shall comply with NFPA13 as regulated by the fire department. CDM
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection9/24/20109/24/20109/24/2010PPASS
DetailsForrest France
Fire alarm permit work okayed for final, address switch repaired while on site. Inspection passed.
INSP-Alarm Testing9/24/20109/24/20109/24/2010PPASS
DetailsForrest France
Reinspection for noted correction items passed at the 2nd, 5th and 6th floors.
INSP-Final Inspection9/23/20109/23/20109/24/2010PFAIL
DetailsForrest France
Correction items include relocate three SD too close to HVAC diffusers, adjust cd setting per plan at one room 5th floor, voice evacuation message does not meet intelligibility or audibility requirements.
INSP-Alarm Testing9/22/20109/22/20109/22/2010APART
DetailsForrest France
After hours inspection scheduled 9/23 PM.